Technical data Modbus
Bus system
Transmission rate
Transmission mode
Bus length (max.)
Response time:
■ The Interface works only if the phase 1 is connected.
■ The communication is ready 30 s after the power on
■ The use of energy meter in Bus with intensive communication could reduce the performance of the Bus
■ Refresh time for the data is 10 s. For this reason one energy meter should be not polled faster as 10 s.
■ 247 devices could be connected to the Modbus. Over 128 devices, a repeater should be used.
■ The interface don't have a terminal resistor, this should be provided external.
■ For a description of the used registers please look at the register page

Data transmission

■ Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized.
■ Up to 20 Registers can be read at a time.
■ The device supports broadcast messages.
■ In accordance with the Modbus protocol, a register R is numbered as R - 1 when transmitted.
■ The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM (transmission rate, etc.)
Exception Responses
■ ILLEGAL FUNCTION [01]: The function code is not supported.
■ ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range
or more than 20 registers have been requested.
■ ILLEGAL DATA VALUE [03]: The value in the data field is invalid for the referenced register.
Change the Modbus address direct on device
■ To modify the Modbus address, press 3 s on ► touch
■ In menu, ▼ increase address by 10, ► increase by 1
■ Once the address is selected wait for the root menu to come back
Modbus, RTU according to IDA specification
4800-9600-19 200-38 400-57 600-115 200.
The transmission Baud rate is automatically detected
Even parity: 8 data bits, 1 stop bit
Odd parity: 8 data bits, 1 stop bit
No parity: 8 data bits, 2 stop bits
The parity is automatically detected
1200 m (without repeater)
Write: 60 ms
Read: 60 ms