SBC AWD3D5WD Instructions De Montage Et D'utilisation page 4

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Registers
For double registers (4 – 5, 16 – 17, 28 – 29, 30 – 31) the high register is sent first (big_Endian).
The Partial counter (30 – 31) can be reset by writing 0 in both registers in the same message.
R
Typ Description
1
R
Firmware-Version
2
R
Number of supported
registers
3
R
Number of supported
flags
4–5
R
Baudrate
6
R
Not Used
7
R
Type / ASN function
8
R
Type / ASN function
9
R
Type / ASN function
10
R
Type / ASN function
11
R
Type / ASN function
12
R
Type / ASN function
13
R
Type / ASN function
14
R
Type / ASN function
15
R
HW vers. Modif.
16–17
R
Serial number
18
R
Serial number
19
R
Not Used
20
R
Not Used
21
R
Not Used
22
R
Status
23
R
Response timeout
24
R/W
1)
Modbus Address
25
R
Error register
26
R
Current Transformer
Ratio
27
R
Not Used
28–29
R
WT1 total High
Counter Energy Total
Tariff 1 High
30–31 R/W WT1 partial
Counter Energy Partial
Tariff 1
32
R
Not Used
Unit
Ex:11 =FW 1.1
Will give 52
Will give 0
Ex: Baudrate High = 1 Baudrate
Low = 49664
1 × 65536 + 49664 =
115'200 bps
Will give 0
Will give «AW»
Will give «D3»
Will give «D5»
Will give «FW»
Will give «00»
Will give «Cx»
x : 2 = Non MID
x : 3 = MID
Will give «A0 »
Will give «0»
Ex: 11 =HW 1.1
Unique 32 bit serial number low
Unique 32 bit serial number high
Will give 0
Will give 0
Will give 0
0 = no Problem
1 = problem with last
communication request
ms
Range 1–247
0 : No error
1 : Error Phase 1
2 : Error Phase 2
3 : Error Phase 1+2
4 : Error Phase 3
5 : Error Phase 1+3
6 : Error Phase 2+3
7 : Error Phase 1, 2+3
Ex: Transformer 100 / 5 give 20
Will give 0
10
kWh (multiplier 0,1)
–1
Ex: WT1 total High = 13
WT1 total Low = 60383
13 × 65536 + 60383 =
912351 = 91235.1 kWh
10
kWh (multiplier 0,1)
–1
Ex: WT1 partial High = 13
WT1 partial Low = 60383
13 × 65536 + 60383 =
1)
912351 = 91235.1 kWh
Will give 0
R
Typ Description
Unit
33
R
Not Used
Will give 0
34
R
Not Used
Will give 0
35
R
Not Used
Will give 0
36
R
URMS phase 1
V
Effective Voltage of
Ex: 230 = 230 V
Phase 1
37
R
IRMS phase 1
A / Except 5/5 = 10
Ex: 314 = 314 A
Effective Current of
Phase 1
38
R
PRMS phase 1
10
Effective active Power
Ex: 1545 = 154,5 kW
of Phase 1
39
R
QRMS phase 1
10
Effective reactive Power
Ex: 1545 = 154,5 kvar
of Phase 1
40
R
cos phi phase 1
10
Ex: 67 = 0,67
41
R
URMS phase 2
V
Effective Voltage of
Ex: 230 = 230 V
Phase 2
42
R
IRMS phase 2
A / Except 5/5 = 10
Effective Current of
Ex: 314 = 314 A
Phase 2
43
R
PRMS phase 2
10
Effective active Power
Ex: 1545 = 154,5 kW
of Phase 2
44
R
QRMS phase 2
10
Effective reactive Power
Ex: 1545 = 154,5 kvar
of Phase 2
45
R
cos phi phase 2
10
Ex: 67 = 0,67
46
R
URMS phase 3
V
Effective Voltage of
Ex: 230 = 230 V
Phase 3
47
R
IRMS phase 3
A / Except 5/5 = 10
Effective Current of
Ex: 314 = 314 A
Phase 3
48
R
PRMS phase 3
10
Effective active Power
Ex: 1545 = 154,5 kW
of Phase 3
49
R
QRMS phase 3
10
Effective reactive Power
Ex: 1545 = 154,5 kvar
of Phase 3
50
R
cos phi phase 3
10
Ex: 67 = 0,67
51
R
PRMS total
10
Effective active Power of
Ex: 1545 = 15,45 kW
all phases
52
R
QRMS total
10
Effective reactive power
Ex: 1545 = 15,45 kvar
of all phases
The Modbus Address register is not writable with a broadcast message.
–1
A
kW (multiplier 0,1)
–1
kvar (multiplier 0,1)
–1
–2
(multiplier 0,01)
A
–1
kW (multiplier 0,1)
–1
kvar (multiplier 0,1)
–1
(multiplier 0,01)
–2
–1
A
kW (multiplier 0,1)
–1
kvar (multiplier 0,1)
–1
–2
(multiplier 0,01)
kW (multiplier 0,1)
–1
kvar (multiplier 0,1)
–1

Publicité

Table des Matières
loading

Produits Connexes pour SBC AWD3D5WD

Table des Matières