P05 *
External fan control
P06 *
Set value start external fan
P07 *
Switching hysteresis external fan
P08
Shut-off delay time external fan
P09 *
Calibration temperature sensor TS1
P10 *
Temperature unit ° C / ° F
Compressor function in the case of sensor
P11
failure
P12 *
Filter monitoring differential value
P13 *
Master / Slave recognition
P14 *
Number of slaves in the system
P15 *
Slave address
P16 *
Ice danger temperature point
P17
Alarm delay
P18
Alarm excessive temperature TS1
Switching point alarm ambient temperature
P19
TS1
P20 *
Limiting value alarm lack of refrigerant
P21 *
Temperature display suction line TS2
P22 *
Temperature display pressure line TS3
Temperature display ambient temperature
P23 *
TS4
A01
Alarm door switch
A02
Alarm excessive internal temperature
A03 *
Alarm filter control
A04 *
Alarm ice danger
A05 **
Alarm high pressure
A06 *
Alarm lack of refrigerant
Alarm temperature sensor TS1
A07
Sensor failure or short circuit
Alarm temperature sensor TS2
A08 *
Sensor failure or short circuit
Alarm temperature sensor TS3
A09 *
Sensor failure or short circuit
Alarm temperature sensor TS4
A10 *
Sensor failure or short circuit
Alarm ambient temperature TS4 –either too
A11 *
high (>56°C) or too low (<15°C)
Alarm phase monitoring / Thermal
A12 **
protection contact
A13
Alarm EEPROM error
A14 *
Alarm master and slave are not connected 0....2
Fault diagnosis display controller KR-HD
Fault diagnosis display controller KR-HD
Parameter-
Error
No:
A01
Alarm door switch
A02
Alarm excessive internal temperature
A03 *
Alarm filter control
A04 *
Alarm ice danger
A05 **
Alarm high pressure
A06 *
Alarm lack of refrigerant
Alarm temperature sensor TS1
A07
Sensor failure or short circuit
Alarm temperature sensor TS2
A08 *
Sensor failure or short circuit
Alarm temperature sensor TS3
A09 *
Sensor failure or short circuit
Alarm temperature sensor TS4
A10 *
Sensor failure or short circuit
Alarm too high or to low ambient
A11 *
temperature TS4
Alarm phase monitoring/thermo
A12 **
contact
A12 **
Alarm: thermal contact
A13
Alarm EEPROM error
Alarm master and slave are not
A14 *
connected
** Not for UL-listed and non-filter equipment
0....1
0
0 = fan function OFF,
1 = fan function ON
25....50
30 °C
If the fan function is switched ON, the external fan starts to operate when
the set value P06/pressure line temperature TS3 is exceeded, and it remains
2....10
2 K
in operation till the value is below the hysteresis level (P07).
If the cooling system is switched OFF or if faults occur, the external fan
0....10
2 minutes
remains in operation until the expiration of the programmed delay time, in
order to cool the vaporizer.
-10...+10
0 K
0 = ° Celsius, 1 = ° Fahrenheit
0....1
0
All absolute temperatures and temperature differences are shown and input
in the adjusted temperature unit.
0 = always OFF,
0....1
1
1 = 10 minutes ON, 10 minutes OFF (emergency cooling)
If the differential temperature pressure value TS3 – ambient temperature - is
10....50
24 K
higher than this value, then alarm A03 is released. The compressor remains
in operation.
0 = Master (all devices are switched off via an open door switch)
1 = Master (only the corresponding slave is switched off via an open door
0....3
3
switch)
2 = Slave
3 = Individual unit
1....15
1
1....15
1
Put in an address for each slave. Start with address 1 without break.
If the temperature at the suction line TS2 falls below this parameter value,
alarm A04 is released and the compressor is switched off. However, the
-5....+10
3 °C
error evaluation starts only 3 minutes after the start of the cooling system. If
the parameter value is exceeded by 5K, normal conditions are sensed.
If an alarm occurs, the assigned relays are switched off with delay. However,
0....120
5 Sec.
the display and perhaps the disconnection of the compressor are effected
immediately.
3 options for excessive temperature alarm - internal cabinet temperature
TS1:
0....2
0
0 = fixed value P19
1 = 10 K over set value
2 = 15 K over set value
Switching point for excessive temperature alarm – internal cabinet
20....60
50 °C
temperature TS1 for option parameter P18 fixed value.
If the difference between the internal cabinet temperature TS1 and the
temperature suction line TS2 is below this limiting value, alarm A06 is
1....30
7 K
released. The cooling system remains in operation. The error evaluation
however, is only effected 3 minutes after the start of the cooling system.
The temperature of the suction line TS2 is shown for 50 sec. on the display.
The temperature of the pressure line TS3 is shown for 50 sec. on the display.
The ambient temperature TS4 is shown for 50 sec. on the display.
0....2
0
0
0....2
1
1
Alarm indications can be individually assigned to the 2 fault indication relays.
0....3
0
3
0 = No relay
0....3
0
2
1 = Relay 1
2 = Relay 2*
0....2
1
1
3 = not assigned/deactivated. By choosing this option, either the sensor
0....3
0
2
entry and all fault indications or switching actions, relating to this sensor or
0....2
1
1
an individual alarm are deactivated.
** Not for UL-listed and non-filter equipment
0....3
3
1
0....3
3
1
0....3
3
1
0....3
0
2
0....3
3 (1) 3
(1) Factory settings for 3-phase units
0....2
1
1
0
2
Device function
Cause of trouble
Internal fan does not
Cabinet door is open or door switch
operate
is wrongly positioned
cooling capacity/size too low
Clogged filter pad
Defective internal fan
Cooling system OFF
Set value too low
Clogged filter/condenser
Defective external fan
Cooling system OFF
Excessive ambient temperature
Leakage
Sensor failure or short circuit
Sensor failure or short circuit
Sensor failure or short circuit
Sensor failure or short circuit
Too high (>56°C) or too low
(<15°C) ambient temperature
Cooling OFF
Phase error
Compressor high temperature /
Cooling OFF
Ambient temperature too high
Default values are not
loaded
If slave cooling system is
switched OFF, master
Connection error or faulty
cooling system remains in
configuration
operation
Remedy
Close cabinet door, adjust door
switch, check connection/install a
bridge
Check installed heat
dissipation/device cooling capacity
Exchange or cleaning
Exchange.
Increase the set value internal
temperature P00
Clean filter/condenser
Replace external fan
Create permissible operating
conditions
Leakage troubleshooting / repair by
experts
Exchange
Exchange
Exchange
Exchange
Create permissible operating
conditions
Check power supply / phase rotation
Check operating paramters
Re-adjust modified parameter
Check cables or configuration
7