60002
Poduct presentation
Load shedding
display
Adjustment
of
load
shedding
threeshold
from 15 to 60 A.
If rated power is exceeded,
output load shedding
takes place immediately.
After 6 minutes, the output
is reconnected.
Installation
Input/output
The load shedding information is sent from output
terminal 1: load shedding results in an OFF signal
being sent
.
Input terminal 2 connected to a heating programmer
with a pilot wire. Where there is no load shedding,
the output retransmits the switching which arrives
at the input.
Current transformer
The current transformer is to be connected to
terminals 5 and 6 by means of the 2 connection wires,
extended over a maximum distance of 5 metres.
Technical characteristics
Supply voltage:
230 V + 10%/- 15%
Frequency:
Power consumption:
Breaking capacity:
Operating temperature:
-10 °C to +50 °C
Storage temperature:
-20 °C to +60 °C
Hygrometry:
Connection by shielded terminals
Sectional area of conductors: 0,5 mm
Complies with the NFC 61.750 standard (load
shedding)
Made in France
2
Hager S.A.S. - 132 bd d'Europe - B.P. 78 - 67212 Obernai cedex (FRANCE) - Tél. +333 88 49 50 50 - www.hagergroup.net
Délesteur
FR
Load shedder
GB
Connection
Programmer
1 zone
(optionnal)
A
15
30
45
60
Pilote wire
Contact heating control
Mounted on DIN rail
50 Hz
2 W max.
1A/230 VAC
90% at 20 °C
2
to 4 mm
2
for single-phase systems with rated powers of
up to 12 kVA.
one load shedder per phase.
way of an OFF command, sent via a pilot wire.
Power control is implemented for 1 circuit, and is
particularly intended for heating. Power draw is
measured using a current transformer supplied
with the load shedder 60002.
Dimensions
N
L
L
5 6
3 4
1 2
The load shedder 60002 is a power controller
For three phase systems, it is possible to use
Heating circuit load shedding is produced by
43,7
59,5
17,8
6T 7710.a