4 - CONTROLS
Available controllers for KAOLYX EPP :
- TS
- HMI
- T-BOX
KAOLYX EPP BC must be used with the Tbox.
4.1 - CONTROL EQUIPMENT
Two-way valve with actuator
Protection degree : IP20
Supply voltage : 230V 50/60Hz
Max. medium temperature : + 93 °C
Max. operating pressure [MPa] : 2,1
3/4" : Kvs [m
/h] : 6,5
3
1/2" : Kvs [m
/h] : 3
3
Open / close runtime : 18s / 5s
Mounting : on the return line of the heat medium from the heater.
Three-way valve with actuator
Protection degree : IP20
Supply voltage : 230V 50/60Hz
Max. medium temperature : + 93 °C
Max. operating pressure [Mpa] : 2,1
Open / close runtime: 18s / 5s
3/4" : Kvs [m
/h] : 6,5
3
1/2" : Kvs [m
/h] : 3,4
3
Mounting : on the supply line of the heating medium to the heater.
NT 1675 H - 09/2018
All manuals and user guides at all-guides.com
Les aérothermes Kaolyx EPP ont trois types de régulation
possibles :
- thermostat TS
- commande HMI
- boîtier Tbox
Les aérothermes Kaolyx EPP BC doivent être obligatoirement
raccordés au boîtier Tbox.
4.1. - LES ELEMENTS D'AUTOMATISME
4 - RÉGULATION
Vanne deux voies avec actionneur
Niveau de protection : IP20
Alimentation : 230 V 50/60 Hz
Température max de fluide : + 93 °C
Pression max [MPa] : 2,1
3/4" : Kvs [m
/h] : 6,5
3
1/2" : Kvs [m
/h] : 3
3
Temps d'ouverture / fermeture : 18s /5s
Montage : sur le retour de fluide thermique d'aérotherme
Vanne à trois voies avec actionneur
Niveau de protection : IP20
Alimentation : 230 V 50/60 Hz
Température max de fluide : + 93 °C
Pression max [MPa] : 2,1
Temps d'ouverture / fermeture : 18s / 5s
3/4" : Kvs [m
/h] : 6,5
3
1/2" : Kvs [m
/h] : 3,4
3
Montage : sur l'entrée d'eau batterie