RS485 Databus Loop Interface
M
OUNTING THE UNIT
The board has a standard ATS 'BB' footprint, mountable in existing ATS
metalwork.
C
J1
ONNECTIONS
COMMS
+12
12 VDC supply input. 80 mA max. with no other peripheral devices
0V
connected.
D+
Positive and negative data connection of the RS485 databus.
D-
Units can be up to 1.5 km from the 4 door DGP or control panel,
depending on the cable used. Recommended WCAT52/54; 2-pair
twisted, shielded, data cable.
C
J2
ONNECTIONS
LOOP START AND
J2
LOOP START Primary side
J3
LOOP END Secondary side
+12
12 VDC supply output.
0 V
D+
Positive and negative data connection of the RS485 databus.
D-
Units can be up to 1.5 km from the 4-door DGP or control panel,
depending on the cable used. Recommended WCAT52/54; 2-pair
twisted, shielded, data cable.
Ground connector
LED'
S
Fault
Red LED. On when RS485 loop is operating in fault tolerant mode.
TX
Yellow LED. On when receiving data from Loop devices
RX
Green LED. On when Loop devices are transmitting to the control
panel.
Interface bouclage de bus de données RS 485
M
'
ONTAGE DE L
UNITE
La carte est au format "BB" standard et peut être installée dans un coffret
Aritech existant.
C
J1
ONNEXIONS COMMS
+12
Entrée 12 VCC
0V
80 mA au maximum sans aucun autre dispositif
D+
Connexion de données positive et négative du bus de données RS485.
D-
Les unités peuvent se trouver à une distance de 1,5 km de la centrale
ou du contrôleur à 4 portes, selon le câble utilisé. WCAT52/54
recommandé ; câble de données blindé avec 2 paires torsadées.
C
J2
ONNEXIONS COMMS
LOOP START ET
J2 LOOP START – Côté principal
J3 LOOP END – Côté secondaire
+12
Sortie 12 VCC
0V
D+
Connexion de données positive et négative du bus de données RS485
J3
LOOP END
J3
LOOP END
© 2003 GE Interlogix B.V.
RS485 Databus Loop Interface
L
INKS
Refer to the ATS Control Panel installation guide. System
TERM
databus term link.
Loop start term link.
TERM
Loop end term link.
TERM
Refer to the ATS Control Panel installation guide LAN system and Earth
Connection Block Diagram.
C
J4 F
ONNECTIONS
Faults
Fault condition indicated by relay contacts.
NC
C
NO
N/O-4k7
When removed, a 4k7 resistance is placed in series with the
N/C contact.
N/C-4k7
When fitted a 4k7 resistance is placed in parallel with the N/C
contact.
A fault is registered when data returning to the Loop End connections is
different from the data sent out through the Loop Start connection.
In this case the ATS Control Panel can detect which, if any, peripherals
connected to the loop have failed. See ATS Control Panel installation
guide Databus Loop Fault Relay to the Control Panel. If a databus fault
occurs, the Fault Relay will be energized on the ATS1742 board, which
can be use to generate an alarm or other pre-programmed response.
Checks are performed every 2 minutes to determine the loop's state.
Once the loop fault is corrected, the relay will be de-energized after a
period of 1.5 to 2 minutes and all internal processes will be reset to pre-
fault conditions.
D-
Les unités peuvent se trouver à une distance de 1,5 km de la centrale
ou du contrôleur à 4 portes, selon le câble utilisé. WCAT52/54
recommandé ; câble de données blindé avec 2 paires torsadées.
Connecteur à la terre
V
OYANTS LUMINEUX
FAULT
Voyant rouge. Allumé lorsque la boucle RS485 fonctionne en mode
tolérance de panne.
TX
Voyant jaune. Allumé lors de la réception de données des dispositifs
sur le bus.
RX
Voyant vert. Allumé lorsque les dispositifs en boucle transmettent
des données vers la centrale.
C
AVALIERS
TERM
Consultez le guide d'installation de la centrale ATS. Cavalier
Term du bus de données du système.
TERM
Cavalier Term du début de boucle
TERM
Cavalier Term de la fin de boucle
Consultez le guide d'installation de la centrale ATS.
All rights reserved
ATS1742
AULT
Normally closed contact.
Closed contact.
Normally open contact.
MAINST-ATS1742
12/2003

Publicité

loading

Sommaire des Matières pour Interlogix ATS1742

  • Page 1 See ATS Control Panel installation LED’ guide Databus Loop Fault Relay to the Control Panel. If a databus fault occurs, the Fault Relay will be energized on the ATS1742 board, which Fault Red LED. On when RS485 loop is operating in fault tolerant mode.
  • Page 2 • Les cavaliers « TERM » doivent être raccordés à Term sur la carte ATS1742. Supprimez tous les cavaliers « TERM » sur les unités DGP et RAS connectées à la boucle locale. • Pour le module Centrale ATS, il est conseillé d’utiliser un câble de données WCAT52/54 blindé...
  • Page 3 Technical Data Specifications Technische Specifiche tecniche Dane techniczne techniques specificaties Operating temperature Température de Bedrijfstemperatuur Temperatura di esercizio Temperatura pracy 0 °C to + 50 °C fonctionnement Humidity Non Humidité sans Vochtigheidsgraad Umidità senza condensa Wilgotność: bez condensing condensation condensvrij kondensacji Power consumption Consommation...