6.2 Transmitter associated functions (switch mode)
The functions associated with different sensors are determined during learning. The learning
process (Cf § 5.1) is to do before activating the transmitter.
designation
Switch
Button 1 (2, 3 or 4) :
pressed and released before
visual acknowledge
1
3
1
Button 1 (2, 3 or 4) :
2
2
4
pressed and released after
visual acknowledge
Button 1 (2, 3 or 4) :
pressed and released before
visual acknowledge followed by,
pressed and released after
visual acknowledge
Key card
Card inserted before the entry into
learning mode, removed (in
learning mode) then reinserted
Window handle
Closed to opened or opened to
closed
Windows contact
Press the LEARN button
Dry contact sensor
Press the LEARN button
Occupancy sensor
Press the LEARN button
Note *: The ON state corresponds to the lighting of the LED (on the front of the product),
contact closure output NO and the opening of the output contact NF.
TOC1404NUaa_0816
All manuals and user guides at all-guides.com
Learning
Function obtained*
Button 1 (or 3) : ON
Button 2 (or 4) : OFF
Button 1 (2, 3 or 4) :
Transition from ON to
OFF and vice Versa
(Switch mode only §6)
Button 1 (2, 3 or 4) :
pressed
: ON
released : OFF
Card inserted : ON
Card removed : OFF
Tilt to opened : no
change
Opened to tilt : no
change
Closed to opened : OFF
Opened to closed : ON
Magnet away : ON
Magnet near : OFF
Contact closed : OFF
Contact open : ON
Detection (PIR = On) :
ON
Detection (PIR = OFF) :
OFF
7. Troubleshooting
7.1 New or existing installation
• Check the circuit breaker, the electrical supply and the load connected to the receiver
associated with this sensor (qualified electricians).
• Check the connected load and the connecting cables (qualified electricians).
• If the receiver functions at a shorter distance relative to the sensor, it is subject to
interference or used outside the transmission range.
• Search the system environment for changes that could cause the interference (for example
movement of metallic cabinets, furniture or partitions).
• Use the sensor or receiver in a more suitable locations.
• Clear the receiver and perform a new learn process.
7.2 Automatic activation of the receiver
• The cause may be the activation of a sensor external to the system which has by chance
been programmed on the receiver.
• Clear the receiver and perform a new learn process.
7.3 Limitation of the range of the radio signals
• Transmitter/receiver used close to metallic objects or close to materials containing metallic
elements. Observe a distance of at least 10cm.
• Humidity in the materials.
• Device emitting high frequency signals such as: audio and video systems, computers,
electronic ballasts or fluorescent tubes. Observe a distance of at least 0,5m.
7.4 Contacts
E-mail:............................
contact@trio2sys.fr
8. Declaration of conformity
This product can be marketed and distributed in the countries of the European Union. Hereby
0
TRI
SYS
2
declares that radio equipment 10020069 is in compliance with directive
2014/53/EU, known as the RED Directive.
The full text of the EU declaration of conformity is available at the following internet address:
www.trio2sys.fr
.
D.Girard
4/4