The CGLine+ Web Compact controller is supplied as standard with the fixed IP address
192.168.1.200.
Operation via dhcp (dynamic IP address assignment) is possible but not factory-activated.
Because typical company networks only permit own-assigned IP addresses, we recommend
configuring network settings via direct connection to a PC, e.g. a notebook.
The network configuration can be done directly on the CGLine+ Web Compact con-
troller. The connection to a PC via a patch cable is optional.
The devices must be in the same subnet, meaning the network card of the PC must be set
to 192.168.1.xxx (not equal to 200), e.g. 192.168.1.50 (subnet to 255.255.255.0).
Settings for gateway and DNS must not be taken into account with a direct connection.
3. FIRST START
a
230V/AC
When the CGLine+ Web
Compact Controller starts, a
loading page appears during
3 seconds.
Then, a recap of the entire
installation appears on
screen. You can detect easily
a failure and identify the line
and zone in which the
problem is.
b
Select User for choosing a
password.
Enter a password of 10
characters maximum.
Then validate with OK.
c
Go back to previous display.
Select Admin for choosing a
password.
Enter a password of 10
characters maximum.
Then validate with OK.
d
The CGLine Web Compact Controller is now ready to be used !
Quick installation manual CGLine+ Web Compact Controller ZNO2050500 PrB 03/2020 www.eaton.com
All manuals and user guides at all-guides.com
CGLine+ Compact
11:40
CGLine+ Compact
Line 1
Line 2
Operation
Blocked
CGLine+ Compact
1.User
CGLine+ Compact
2.Administrator
Z1
Z2
Z3
Z4
Failure
Test
No luminaire
Login
11:40
21/01/2020
Login : User
Password
X
Cancel
11:40
21/01/2020
Login : Admin
Password
X
Cancel
Ok
Ok