IMPORTANT
Check whether it concerns an AC(Alterna ng Current) based or DC(Direct Current) based system.
6
NEMA Socket
ELECTRICAL CONNECTIONS - 100-240V/277V AC, 50/60Hz
PHASE TO NEUTRAL WIRING
STEP 1:
Make the following Electrical Connec ons:
a.
Connect INPUT GROUND conductor to middle posi on
of the female power turn off protector plug.
b.
Connect INPUT VOLTAGE conductor to "L" posi on
of the female power turn off protector plug.
c.
Connect INPUT NEUTRAL conductor to "N"posi on
of the female power turn off protector plug.
STEP 2:
Make sure all excess input wires are pushed into pole, screws are
ghtened.
STEP 3:
Close cover by firmly pushing cover towards fixture, making sure
that no wires are pinched and Sealing gasket are fully engaged.
ELECTRICAL CONNECTIONS - 100-240V/277V AC, 50/60Hz
PHASE TO NEUTRAL WIRING
STEP 1:
Make the following Electrical Connec ons:
a.
Connect INPUT VOLTAGE conductor to "L" posi on
of the female power turn off protector plug.
b.
Connect INPUT NEUTRAL conductor to "N"posi on
of the female power turn off protector plug.
STEP 2:
Make sure all excess input wires are pushed into pole, screws are
ghtened.
STEP 3:
Close cover by firmly pushing cover towards fixture, making sure
that no wires are pinched and Sealing gasket are fully engaged.
This marking indicates that this product should not be disposed with other household wastes throughout the EU.
To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it
responsibly to promote the sustainable reuse of material resources. To return your used device, please use
the return and collec on systems or contact the retailer where the product was purchased. They can take
this product for environmental safe recycling.
REV170224CLZ-01
PHOTOCELL (OPTIONAL)
If the fixture with PHOTOCELL func on, the NEMA Socket will be installed on the
cover of fixture. See
rotate Photocell to proper posi on.
<Verifying>
Make sure all the connec ons done and photocell is well installed on the fixture,
switch on the power supply and cover the window of photocell, wait 5 seconds,
the fixture will be turned on.
Photocell
6
. Fit the pins of Photocell to NEMA Socket, firmly insert and
Input cable should be at least H05RN-F 3x1.0mm²(SJTW 18AWG) or
outdoor grade cable with rubber sheathed(not supplied). The cable
must have a minimum cross sec onal area of 1.0mm²(18AWG).
FIXTURE WIRING
N
L
V
in
N
L
*If the fixture with built-in 3 in 1 dimming func on, please connect INPUT
POSITIVE(+) signal conductor to DIM+ (PURPLE WIRE), INPUT NEGATIVE(-) signal
conductor to DIM-(GREY WIRE) of LED driver.
FIXTURE WIRING
N
L
V
N
L
*If the fixture with built-in 3 in 1 dimming func on, please connect INPUT
POSITIVE(+) signal conductor to DIM+ (PURPLE WIRE), INPUT NEGATIVE(-) signal
conductor to DIM-(GREY WIRE) of LED driver.
Class I BASED
LED Driver
V
out
Class II BASED
LED Driver
V
in
out