CHLORIDE LINEAR Plus/RM
Return from maintenance bypass procedure - Linear
Plus 6/10 kVA
Ensure all switches and circuit breakers upstream of the UPS are
closed.
Switch both Input Switch to position (I) ON.
Wait for at least 30 seconds until the output voltage has stabilized
(yellow bypass LED illuminated).
Switch the Maintenance switch (see Fig. 9 on page EN-24 and Fig. 11
on page EN-25) from „BYPASS" to "UPS" and replace the cover. The
load now is supplied via electronic bypass.
Press the "MENU" button, select submenu "Control" and press "OK",
select submenu "Turn UPS ON/OFF" and press "OK", the LCD displays
"Turn UPS to ONLINE" then press "OK" to switch on the inverter (see
"Control panel Linear Plus" on page EN-36). The UPS is now in ON-
LINE operation.
Maintenance Switch, position "OFF"
Switch to "OFF" position to disconnect the UPS output from an output
distribution, i.e. in a parallel operating UPS system.
Danger
Connected loads are not supplied if the Maintenance Switch is set to the
"OFF" position
UPS start-up procedure Linear Plus RM
Ensure all switches and circuit breakers upstream of the UPS are
closed.
Switch Input Switch to position (I) ON.
User Handbook SU59802UM01, rev.3/ Last modified: 08/2005
Operating the Device
EN-51