Table 1. Temperature correction factors
°C
5
7
10
11
14
15
16
19
20
25
26
29
30
Example:
RO unit
Production flow
Permeate preesure
Feed pressure
Temperature
Net operating pressure
Pressure compensated flow rate
Temperature compensated flow rate = 0,34 x 1,37 = 0,465 m³/h
When the compensated flow decreases by 10% or more or the product TDS increases by 10%, membrane
cleaning should be scheduled.
With aging of the membranes there will also be a gradual decline in production flow. Thus, the age of the
membranes should also be taken into account. In general, there is a loss of production of:
Age
6 months
1 year
3 years
4.17
FILTER CARTRIDGES
The supplied filter cartridges have a 5 micron sieve. They must be replaced when the pressure drop across
the filter cartridge exceeds 0.7 bar or if they are discolored. The prefilters are placed to protect the membra-
nes and should therefore be properly checked.
4.18
CHEMICAL INJECTION SYSTEMS
Dosage devices for dosing anti-scalent should be checked regularly for their proper functioning. The dosing
pump can draw air or get contaminated with eg sand particles. These dosages also serve to protect the mem-
TCF (25°C standard)
2,08
1,92
1,71
1,63
1,48
1,42
1,37
1,24
1,19
1,00
0,97
0,89
0,86
4002
0,45 m³/h
0,35 bar
11,7 bar
16°C
= 11,7 – 0,35 = 11,35 bar
= 0,45 x 8,6 / 11,35 = 0,340 m³/h
Production loss
7%
12%
17 %
TCF (15°C standard)
1,54
1,41
1,24
1,19
1,04
1,00
0,97
0,88
0,86
0,74
0,71
0,65
0,64
42