General electrical data
Degree of protection
Class of protection
Leakage current to PE
MTBF
to IEC 1709 (SN 29 500)
Max. power loss
(idle state/ rated load)
Efficiency
at AC 230 V and rated values
Input data
Turn−on time
Transient surge voltage protection
Mains voltage range
Current
consumption
Starting current limitation /
2
I
t (+25 °C)
Mains buffering at
rated load
Recommended back−up fuse
circuit−breaker
(characteristic B or C)
EDKZV1200 DE/EN/FR/ES/IT 1.0
5 A
IP 20
I (with PE connection)
< 3.5 mA
> 500 000 h
2 W / 14 W
> 89 %
5 A
< 1 s after applying the mains voltage
varistor
AC 85 V − 0 % ... 264 V + 0 %, 45 Hz − 0 % ... 65 Hz + 0 %
AC 120 V 1.6 A
AC 230 V 0.8 A
typ. < 15 A /
2
< 2.5 A
s
AC 120 V typ. > 20 ms
AC 230 V typ. > 120 ms
6 A / 10 A / 16 A
l
Technical data
Power supply unit AC 230 V, DC 24 V
10 A
2 W / 24 W
> 91 %
Power supply unit AC 230 V, DC 24 V
10 A
2.3 A
1.2 A
typ. < 15 A /
2
< 1.5 A
s
typ. > 50 ms
−
3
20 A
3 W / 44 W
> 92 %
20 A
4.8 A
2.3 A
typ. < 15 A /
2
< 3.2 A
s
typ. > 30 ms
−
25