Ceramic cartridge Ø 35mm:
• Basin mixer: flow rate limited to 5 lpm at 3 bar.
ADJUSTING THE TEMPERATURE
Temperature limiter:
• All hospital mixers are fitted with the maximum temperature limiter pre-set at the factory.
Where thermostatic mixing valves are installed the temperature limiter
MUST BE REMOVED from all point-of-use mixers.
• Recommended maximum temperature settings for UK healthcare applications are: bidets 38°C,
washbasins and showers 41°C. For all other countries please refer to the relevant hot water safety guidelines.
Adjusting the mixed water temperature limiter:
To adjust the pre-set maximum temperature, unclip and reposition the index ring located
beneath the control lever.
• The position of the index ring will limit the water temperature at the mixer outlet.
• To access the cartridge (Fig. E1,
unscrew the grub screw b using a 2.5mm Allen key, and unscrew the collar c from the mixer body.
Remove the plastic nut .
• To change the hot water (HW) setting (Fig.
to lower the temperature, or anti-clockwise to increase it. Replace the index ring and check
the temperature at the mixed water outlet to achieve the desired maximum temperature.
• To return to the maximum hot water position (Fig.
with the marker on the cartridge c.
MAINTENANCE
• Our mixers will withstand thermal and chemical shocks as described by current guidelines.
• Check the operation of the cartridge at least once a year, and more frequently if necessary.
In case of malfunction, replace the cartridge.
• Non-return valves and filters must be checked at least once a year and more often if the water quality
necessitates. In the event of malfunction, de-scale or replace worn or damaged parts.
• Across all mixers, the torque required to hold the cartridge in the mixer body should be between
8 and 10 Nm to avoid leaks.
Note: In the event of a leak on the mixers with swivel spouts, replace the 2 waterproof lip seals.
MAINTENANCE & CLEANING
• Cleaning chrome and stainless steel: do not use abrasive, chlorine or any other acid-based cleaning
products. Clean with mild soapy water using a cloth or a sponge.
• Frost protection: drain the pipes and operate the mixer/tap/valve several times to drain any remaining water.
In the event of prolonged exposure to frost, we recommend taking the mechanisms apart and storing them
indoors.
For the UK market only: Tel. 01491 821 821 - email: technical@delabie.co.uk
For all other markets: Tel. +33 (0)3 22 60 22 74 - email: sav@delabie.fr
E2
and E3), remove the control lever by removing the cover cap a,
After Sales Care Support:
The installation guide is available on: www.delabie.co.uk
The installation guide is available on: www.delabie.com
F1
and G1), unclip the index ring a and turn clockwise
F2
and G2), align the marker on the index ring b