3.2
Indicadores LED en estados de Alarma
Cuando el LED de alarma este encendido, observe la barra de LEDs (de izquierda a derecha), y contacte a su agente
de servicio técnico.
LED 1,2 encendidos Sobre voltaje en el inversor
LED 1,3 encendidos
Bajo voltaje en el inversor
LED 1,4 encendidos
Recalentamiento
LED 1,5 encendidos
Sobre voltaje en el cargador
LED 1,2,4 encendidos Corto circuito a la salida
LED 1,2,5 encendidos Sobre voltaje en el BUS
LED 1,3,5 encendidos Mal funcionamiento del PFC o del cargador
LED 1,4,5 encendidos Sobre carga durante operación en el modo batería
Especificaciones Técnicas
Modelo
Capacidad
Operación
Voltaje
Corriente
Entrada
Frecuencia
Factor de poder
Fase
Voltaje
Frecuencia
Forma de onda
Salida
Stable
Sobrecarga
Peak current
Tiempo de transferencia
Voltaje DC
Cantidad
Batería
Corriente de carga
Tiempo de respaldo
Tiempo de recarga
Descarga de la Batería
Descarga por más de 30 min
Alarmas
Batería baja
Sobrecarga
Falla
Ruido Acústico
Temperatura
Ambiente
Humedad relativa
Altitud
Dimensiones
Peso Neto
OMEGA 1000
OMEGA 2000
OMEGA 3000
1000VA/700W
2000 VA / 1400 W
3000VA/2100W
UPS On Line de alta frecuencia
160-270VAC
6A max
12A max
50(60)Hz+/-5%
>0.95 (a máxima carga)
Mono Fásico / H+N+GND
220/230/240VAC+/-2%
50(60)Hz+/-0.5%
Verdadera onda senosoidal
110-140% por 20 segundos
>140% por 10 ciclos
Modo Principal #$ Modo Batería : 0mS
Modo Inversor #$ Modo Bypass : <4mS
48VDC
72 VDC
12VDC/7AH×4pcs
12VDC/7AH×6pcs
12VDC/7AH×10pcs
1A
10~15 Minutos (Depende del tamaño de la carga)
8~10 Horas (Recupera hasta el 90% de la capacidad)
Suena cada 4 segundos
Suena cada 15 segundos
Suena cada segunda
Suena muy rápido
Suena continuamente
<45dBA(1 metros)
<50dBA(1 metros)
0-40°C
0-40°C
<95%(sin condensar)
<3000 metros
(D)467mm×
(D)532mm×
(D)470mm×
(W)190mm×
(W)190mm×
(W)225mm×
(H)255mm
(H)255mm
22Kgs
29Kgs
15
IMPORTANT SAFETY INSTRUCTIONS
UL Safety instructions
! SAVE THESE INSTRUCTIONS - This manual contains important instructions for model 1KVA/2KVA that should
be followed during installation and maintenance of the UPS and batteries.
! When replacing batteries, use the same number and type of batteries.
! Controlled Environment-Intended for installation in a controlled environment. Refer to manual for environmental
conditions.
! CAUTION - Do not dispose of battery or batteries in fire. The battery may explode.
! CAUTION - Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes.
! CAUTION - A battery can present risk of electric shock and high short circuit current. The following precautions
should be observed when working on batteries.
(1) Remove watches, rings, or other metal object.
(2) Use tools with insulated handles.
(3) Wear rubber gloves and boots.
(4) Do not lay tools or metal parts on the top of batteries.
(5) Disconnect charging source prior to connecting or disconnecting battery terminals.
! CAUTION - Servicing of Battery Bank Connection should be performed by service personnel knowledgeable of
batteries and the required precautions. Keep unauthorized personnel away from batteries.
! No User Serviceable Parts -"CAUTION- Risk of electric shock. Do not remove cover. No user serviceable parts
inside. Refer servicing to qualified service personnel."
16A max
! UPS Having Internal Battery -"CAUTION- Risk of electric shock-hazardous live parts inside this UPS are
energized from the battery supply even when the input ac power is disconnected."
! Non-isolated Battery Supply -"CAUTION- Risk of electric shock. Battery circuit is not isolated from AC input,
hazardous voltage may exist between terminals and ground. Test before touching."
! Battery Supplies Over 60V - "DANGER- Risk of electric shock, Do not touch un insulated battery terminals. "
FCC statement
! This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this
device may not cause harmful interference. And (2) this device must accept any interference received including
interference that may cause undesired operation.
120VDC
! Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
-Reorient or relocate the receiving antenna.
-Increase the separation into an on a circuit different from that to which the receiver is connected.
-Consult the dealer or an experienced radio/TV technician for help.
Getting Started
0-40°C
This chapter gives an overview of the features and first-time operating instructions of the Uninterruptible Power
System(UPS).
1.1 Overview
(H)480mm
The purpose of this UPS is to supply power to computers and other electronic equipment after a power failure.
49Kgs
In addition, this UPS protects the equipment from ac power line irregularities such as blackouts, sags, spikes, and
electromagnetic and radio frequency interference. It allows continuous operation through most commercial ac power
disturbances and an
This UPS using the most advanced PWM technology, Long back up time model is available, it includes 10A charger
can rapidly charge the external battery bank.
opportunity to secure data and safely shut down systems in the event of an extended outage.