ATD Series, ATU Series, ATP Series Line Voltage
DESCRIPTION
Hubbell Adaptive Technology (AT series) ceiling mount occupancy sensors
are designed to reduce installation time and prevent callbacks resulting from
improper sensor adjustment. Hubbell AT series sensors study their environment
and automatically adjust the time delay and sensitivity to optimize the sensor's
performance for the specific application.
Each sensor is supplied with the hardware necessary for box mounting.
FEATURES
• Adaptive Technology reduces installation time and prevents callbacks.
• Available in passive infrared (ATP series), ultrasonic (ATU series), dual
technology - passive infrared and ultrasonic (ATD series) models.
• Various models available for coverage areas from 500 to 2000 square
feet.
• Visual motion indicators: ultrasonic-green LED, passive infrared-red LED.
PRE-INSTALLATION
1. NOTICE: For installation by a qualified electrician in accordance with
national and local codes and the following instructions.
2. NOTICE: For indoor use only.
3. CAUTION: RISK OF ELECTRIC SHOCK. Disconnect power before
installing. Never wire energized electrical components.
4. CAUTION: USE COPPER CONDUCTORS ONLY.
5. Check to see that the device's rating is suitable for the application.
6. NOTICE: Do not install if any damage to product is noted.
COVERAGE AND PLACEMENT
The patterns of coverage for the AT sensors are provided at right.
• The sensors must be mounted at least 4' from HVAC vents to avoid air
current interference.
• For interior use only. These sensors should NOT be installed in damp
locations such as near a shower or steam source, in wet locations, or
where exposed to rain.
• Do NOT install in view of strong direct or reflected light sources.
INSTALLATION
1. Turn power off at the service panel.
2. If power pack is shipped with sensor, disconnect sensor from power
pack by rotating the sensor until it unlocks, then disconnecting the
Quick-to-Install (QTI) connectors.
3. Electrically connect the power pack to the building and load wiring as
shown in the wiring diagram. Use approved wire nuts for all electrical
connections (Fig. 1).
4. Mount power pack (CU300AB) directly to 4" octagonal box 2-1/8" deep
or to a 4" square box 2-1/8" deep with round mud ring (Fig. 2). Use
screws (not included) as appropriate to application.
5. Connect sensor to power pack using QTI connector.
6. Tuck QTI connector into pocket of power pack cover plate.
7. Twist sensor on to power pack mounting plate until secured (Fig. 3).
8. Restore power at the service panel.
9. Confirm the correct coverage by simulating motion in the coverage area
which will be typical for the application. If the desired coverage is not
achieved, relocate the sensor to produce the desired coverage. Test the
sensor. To locate the test knob, remove the lens retainer and lens. Turn
the black timer knob fully counterclockwise from any clockwise position.
Replace lens and retainer. The lights will now turn off 8 seconds after
motion stops. Reset timer for application. When installing sensors which
use passive infrared detection, the coverage pattern can be modified
through the use of a lens mask.
White
Neutral
Red
Black
Hot
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD2549
(PAGE 1)
Adaptive Technology Sensors
®
Installation Instructions
Fig.1
Red
04/13
ULTRASONIC
Major
Minor
Motion
Motion
INFRARED
Minor
Major
Motion
Motion
0 5 10 15 20 25 30 35 40 45 50 55 60
0
5
10
15
20
25
30
35
40
45
ATD2000CL
22'
CU300AB
Lighting
Load
12'
22'
ATP1500CL
0 5 10 15 20 25 30 35
0
5
10
15
20
12'
25
22'
30
35
40
ATD1000CL
45
22'
12'
22'
Fig. 2
English
6.5'
13.5'
ATP600CL
23'
32'
ATU1000CL
45'
64'
ATU2000CL
Fig.3

Publicité

loading