G
®
RHEASGARD
KLGF 1
TECHNICAL DATA
Type
Item No.
Operating voltage
Voltage tolerance
Overvoltage category
Signal indication, voltage
Power consumption max.
Device ambient temperature
Signal output flow in V
Accuracy of output signal
Reproducibility of output signal
Media temperature range
Temperature gradient
Switchpoint
Measuring range
Measuring sensor
Immersion depth
Process connection
Sensor material
Pressure resistance
Protection type, housing
Protection type, sensor
Contamination class
Connection
Housing dimensions
Test mark
Accessories
Reference conditions:
Inlet zone >10 x DN, outflow zone >5 x DN, laminar flow: air at 0 °C and 1.013 bar
KLGF 1
24 V AC ⁄ DC
+ 10%
II
mains voltage existing
max. 2 VA
–20..+60 °C
0..10 V (Ra =10 kOhm) relative
+ ⁄ - 10% MW
± 1%
0..+ 70 °C
15 K ⁄ min
adjustable via potentiometer
0,1- 30 m ⁄ s
built-in
130 mm
PG7, mounting flange
MS 58, nickel-plated
10 bar
IP 65
IP 67
II
3 terminals, 2.5 mm
without display: 72 x 64 x 37.8 mm (Tyr 1)
with display : 108 x 70 x 73.5 mm (Thor II)
0
mounting flange
12
2