22
Electrical specifications:
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage universal ............................. 24...230 VAC ±10%
Internal consumption................................... ≤ 2 W (2 channels)
Max. consumption....................................... ≤ 2 W (2 channels)
Fuse ............................................................. 400 mA SB / 250 VAC
Isolation voltage, test / operation................ 3.75 kVAC / 250 VAC
Long-term stability, better than ................... ±0.1% of span / Year
Signal / noise ratio....................................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%) .......... < 25 ms
Calibration temperature............................... 20...28°C
Accuracy, the greater of general and basic values:
General values
Absolute
Input type
accuracy
≤ ±0.1% of span
mA
Basic values
Basic
Input type
accuracy
≤ ±16 µA
mA
50...60 Hz
24...250 VDC ±20%
Temperature
coefficient
≤ ±0.01% of span / °C
Temperature
coefficient
≤ ±1.6 µA/°C
23