To enter setting mode, press the "SET" button and the temperature
display will start flashing.
1.
pressing the up/down arrows (range 16.0 to 40.0°C). When the
desired value is displayed, press the "SET" button once to advance
to cooling differential setting.
2.
pressing the up/down arrows (range 0.3 to 16.0°C). When the desired
value is displayed, press the "SET" button once to advance to
heating differential setting.
3.
pressing the up/down arrows (range 0.3 to 16.0°C). When the desired
value is displayed, press the "SET" button once to advance to alarm
differential setting.
4.
the up/down arrows (range 0.5 to 5.0°C). When the desired value is
displayed, press the "SET" button once to complete setting.
Example:
alarm set for 25°C +/- 0.7°C.
•
•
•
•
As the temperature in the aquarium rises, when it gets above 25.3°C,
the cooling power socket will be energized and the attached fan/
chiller will switch on (after 3 minute short cycle delay). The cooling
power socket will remain energised until the aquarium temperature
reaches 25.0°C.
As the temperature in the aquarium falls, when it gets below 24.7°C,
the heating power socket will be energized and the attached heater
6
Target temperature – can be adjusted to the target value by
Cooling Differential – can be adjusted to the target value by
Heating Differential – can be adjusted to the target value by
Alarm Differential – can be adjusted to the target value by pressing
Set the desired temperature to 25.0°C +/- 0.3°C, with an
The target temperature is set to 25.0°C as above.
The cooling differential is set to 0.3°C as above.
The heating differential is set to 0.3°C as above.
The alarm differential is set to 0.7°C as above.