Electrical Installation - G-U SECURY 21 EK Notice De Montage

Masquer les pouces Voir aussi pour SECURY 21 EK:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.3

Electrical installation

Installation SECURY 2170 / 2170 EVP/ 2171 / 2178 / 2116 S / 2116 S EVP / 2119 S
4
5
6
7
9
8
6
Installation conditions
Supplied connecting cable (from multi-point lock to junction box):
Art. no. B 5490 0300, length 10 m, type LiYY 14 x 0.14 mm²
(SECURY 21 S: Art. no. B 5490 0001, length 8 m, type LiYY 6 x 0.14 mm²)
White (minus)
Brown (plus)
External
control contact
e.g.:
 intercom
 door opener button
 access control
 time switch, etc.
Wiring diagram SECURY 2170 / 2170 EVP / 2171 / 2178
1
see wiring diagram below
2
3
1
Supply line
2
Junction box
(connection see wiring
diagram)
3
Cable duct
or SECUREconnect
4
Cable path
5
1-leaf: SECURY 2170 /
2-leaf: SECURY 2171 / 2119 S
6
Latchbolt pocket
7
Lock pocket
8
Cable loop
9
Escape door strike and
latchbolt pocket EVP
(only 1970 EVP / 1916 S EVP)
Cable cross section
(for customer-provided cable
from junction box)
Length
up to
(–)
(+)
10 m
12-24 V DC,
40 m
stabilised
50 m
External
operating
75 m
voltage
125 m
2170 EVP / 2178 /
2116 S / 2116 S EVP
Cross section
0.5 mm²
0.75 mm²
1.0 mm²
1.5 mm²
2.5 mm²
43