Télécharger Imprimer la page
Lutron PowPak FCJS-010 Installation
Lutron PowPak FCJS-010 Installation

Lutron PowPak FCJS-010 Installation

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

PowPak Fixture Controls
Installation
Part of the Vive Family
FCJS-010
120 – 277 V~ 50 / 60 Hz 1 A switching
FCJS-010-EM
6 mA sink/source
0 –10 V-
FCJS-ECO
120 – 277 V~ 50 / 60 Hz 1 A switching
FCJS-ECO-EM
14 V- 6 mA
Lutron EcoSystem
PowPak Wireless Fixture Control
UL 2043 Plenum Rated
UL 924 Listed (FCJS-010-EM / FCJS-ECO-EM)
Controls up to 3 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or
driver to limit the sink/source current draw to 2.0 mA maximum).
Provides IEC SELV / NECR Class 2, 12 V-, 25 mA to a PowPak fixture sensor
(FC-SENSOR or FC-VSENSOR).
Note for Replacement:
FCJS - the "S" model can replace the non-"S" model
Important Notes:
Please read before installing.
• For installation by a qualified electrician in accordance with all local and
national electrical codes (including periodic testing and maintenance of
emergency systems).
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 32 °F and 104 °F (0 °C and 40 °C), ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
PowPak
Fixture Control
Install the fixture control directly to
a fixture or on a junction box nearest
to the fixture. Install the sensor on the ceiling near
the fixture to optimize coverage in the desired area.
Sensor
Fixture
30 ft (9 m)
Control
maximum
Pico
remote
control
Wireless sensors
and controls must be
located within 60 ft (18 m)
line of sight, or 30 ft (9 m), through
walls, of the associated control module.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS.
• Do not use outdoors.
• Do not mount near gas or electric heaters.
• Equipment should be mounted in locations and at heights where it will not be
subjected to tampering by unauthorized personnel.
• The use of accessory equipment not recommended by the manufacturer may cause
an unsafe condition.
• Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS
For more information please refer to Lutron P/N 369918 at
www.lutron.com
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Required Components
For each fixture, you will need:
At least one of these transmitters (22 total allowed)
One Fixture Control
041645
Rev. A
03/2018
Raise
Load
Laser
Status
Detection
Toggle
LED
+
Lower
PowPak Fixture Sensor
PowPak Wireless Fixture Control
(FC-SENSOR or
(FCJS-010 / FCJS-010-EM or
FC-VSENSOR)
FCJS-ECO / FCJS-ECO-EM)
(1 maximum)
Start Here
1
Install Fixture Control and Optional Fixture Sensor
Suggested Installation Location: Close to the Fixture / Troffer.
WARNING! Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
The fixture control can be installed on a fixture/troffer, junction box or marshalling box
using the conduit nut (provided) or with mounting screws (not provided). Product must
NOT be mounted inside a fixture - only on the exterior of a fixture. Please consult local
and national electric codes for proper installation.
A
Ideally, mount the sensor to the ceiling tile close to the fixture using the wireform or using
the adhesive strip (included). The two communication wires from the sensor attach to the
fixture control stab-in connectors. The wires are interchangeable to eliminate miswiring.
Note: For FC-SENSOR and FC-VSENSOR installation guide visit www.lutron.com
B
Once installed, energize the control module. The fixture will turn on.
Important Note: To optimize RF performance of the product:
– Keep the lamp wiring as short as possible to reduce the
radiation from the lamp wires.
– Keep the lamp wiring as far as possible from the PowPak
Wireless Fixture Control mounting location.
See the Troubleshooting section for more details.
120 / 277 V~ Normal Feed
Neutral
Regular
120 / 277 V~ Generator /
Utility Power
Emergency Feed
Neutral
Note: For periodic testing and maintanance of emergency systems, use
the toggle button of the FCJS-010-EM / FCJS-ECO-EM to ensure
proper operation. Make sure PowPak buttons remain accessible.
Note: Momentary power outages can envoke emergency mode on the
fixture controller. See Troubleshooting section for details.
Emergency
Backup Generator
2
Programming with a Vive Hub
A
B
Use an iOS
or Android
Download the Lutron
®
®
compatible device.
Vive app.
Vive
PIR Lens
Notes:
1. Fixture control can be used
without a fixture sensor as long
Daylight Lens
as at least one Radio Powr
Savr sensor or Pico remote
control is used.
2. Only one fixture control can be
used per fixture sensor, and
only one fixture sensor can be
used per fixture control.
Radio Powr Savr
Occupancy/Vacancy
Sensor
(10 maximum)
Line/Hot (Black)
Neutral
Fixture/
Troffer or
Junction
Box
1/2 in (21 mm)
Knockout
Opening
Conduit Nut
PowPak Fixture
Control Wiring
PowPak Fixture
Control Knockout
Maximize Distance
Lamp
Wiring
Line/Hot (Black)
Neutral
Fixture/
Troffer or
Junction
120 / 277 V~
Box
Emergency Feed
1/2 in (21 mm)
Automatic
Knockout
Transfer
Neutral
Opening
Switch
Conduit Nut
C
Open the app and follow the
instructions.
vive.lutron.com
Customer Assistance
FCJS-010 / FCJS-010-EM: At least one 0 –10 V- Fluorescent Ballast or LED Driver
FCJS-ECO / FCJS-ECO-EM: At least one Lutron EcoSystem Ballast or LED Driver
Consult the fixture installation guide for fixture wiring.
For mounting and wiring best practices see Lutron Application Note #620 (P/N 048620).
+
Pico
6 mA maximum for the control lines. Switches up to 1 A total (or
Radio Powr Savr
Remote Control
maximum 3 ballasts or drivers). May be pre-installed in fixture.
Daylight Sensor
(10 maximum)
(1 maximum)
Note: All drivers and ballasts used with Vive wireless controls must
comply with the limits for a Class A device, pursuant to Part 15 of the
FCC rules.
Reset Factory Defaults
Green/Yellow
Fixture Earth
Neutral (White)
Note: In some instances, it may be necessary to reset the fi xture
N
controls and connected devices back to factory default settings.
Switched Line/Hot (Red)
L
Before beginning, make sure that all devices are connected and
Normal
powered.
Driver / Ballast
A Rapidly tap the Toggle button " u" on the fi xture control three
times and hold on the fourth until the LED begins to flash slowly;
release button.
FCJS-010: – (Gray), + (Violet)
B Within 3 seconds of the start of flashing, again rapidly tap the
FCJS-ECO: E1 (Violet), E2 (Violet)
Toggle button " u" three times and the LEDs will flash rapidly
indicating that the unit has been reset to factory defaults.
Note: Any associations or programming previously set up
with the fi xture control will be erased and will need to be
re-programmed.
From back of
sensor
Notes:
1. Control wires (Violet/Gray for FCJS-010 / FCJS-010-EM or
Violet/Violet for FCJS-ECO / FCJS-ECO-EM) can be run as
Green/Yellow
either Class 1 or Class 2.
Fixture Earth
Neutral (White)
2. If hanging pendant fixtures the maximum wire length
N
Switched Line/Hot (Red)
between fixture sensor and fixture control is 12 ft (3.7 m).
L
Sensor should be mounted no more than 2 ft (0.6 m) from
Emergency
the fixture.
Driver / Ballast
3. To install unit inside a junction box, please see Lutron
Application Note #423 (P/N 048423) on www.lutron.com
FCJS-010-EM: – (Gray), + (Violet)
4. When not using the Vive Hub, the fixture control needs to
FCJS-ECO-EM: E1 (Violet), E2 (Violet)
be accessible for some programming steps. Record where
it is mounted so that it can be easily located later.
5. When using a Radio Powr Savr daylight sensor in
conjunction with both a PowPak wireless fixture control
FCJS-010-EM /
FCJS-ECO-EM only
and PowPak fixture sensor, the Radio Powr Savr daylight
sensor will provide the daylighting input to the control
From back of
sensor
module, and the PowPak fixture sensor daylighting input
will be ignored.
6. When using a Radio Powr Savr occupancy sensor in
conjunction with both a PowPak wireless fixture control
and PowPak fixture sensor, occupancy data from both
Note: For further information on set up,
sensors is used; either one detecting occupancy will
programming, and troubleshooting with a
Vive system, please refer to the installation
turn the lights on, and the lights turn off only when both
instructions included with the Vive hub or
sensors have gone vacant (no longer detect occupancy).
visit www.lutron.com/vive
Note: For programming the PowPak Fixture
7. For more information on the PowPak fixture sensor, see:
Control Module without a Vive hub see the
P/N 369866 or P/N 048556 on www.lutron.com
reverse side.
For FC-SENSOR and FC-VSENSOR installation guide visit
www.lutron.com
www.lutron.com/support

Publicité

loading

Sommaire des Matières pour Lutron PowPak FCJS-010

  • Page 1 Consult the fixture installation guide for fixture wiring. Notes: 03/2018 Raise 1. Fixture control can be used For mounting and wiring best practices see Lutron Application Note #620 (P/N 048620). Load Laser without a fixture sensor as long Status FCJS-010...
  • Page 2 Lutron, EcoSystem, Pico, PowPak, and Vive are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. iOS is a registered trademark of Cisco in the U.S. and other countries and is used under license. Google is a registered trademark and Android and Chrome are trademarks of Google Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. ©2014 – 2018 Lutron Electronics Co., Inc.
  • Page 3 FCJS-010 / FCJS-010-EM: Au moins un ballast fluorescent ou un pilote de DEL de 0 –10 V- Au moins un de ces transmetteurs (22 permis au total) Une commande de luminaire FCJS-ECO / FCJS-ECO-EM: Au moins un pilote de DEL ou ballast EcoSystem de Lutron 041645 Appartient à la famille Vive Consultez le guide d’installation du luminaire pour le câblage du luminaire.
  • Page 4 Cisco aux États-Unis et dans d’autres pays, utilisée sous licence. Google est une marque déposée et Android et Chrome sont des marques de Google Inc. NEC est une marque déposée de le National Fire Protection Association, Quincy, Massachusetts. ©2014...
  • Page 5 FCJS-010 / FCJS-010-EM: Al menos un balasto fluorescente o controlador de LED de 0 –10 V- Al menos uno de estos transmisores (permitidos 22 en total) Un control de artefactos FCJS-ECO / FCJS-ECO-EM: Al menos un balasto o controlador de LED Lutron EcoSystem 041645 Parte de la familia Vive Para informarse del cableado de los artefactos consulte la guía de instalación de artefactos.
  • Page 6 Google es una marca comercial registrada y Android y Chrome son marcas comerciales de Google Inc. NEC es una marca comercial de el National Fire Protection Association, Quincy, Massachusetts. ©2014 –...

Ce manuel est également adapté pour:

Powpak fcjs-010-emPowpak fcjs-ecoPowpak fcjs-eco-em