this Function. Don't change this value when you are not using
a prescaler!
Default : 1-1
Range
F17 : Display (backlight) mode. Duration of backlight activation in
seconds after pressing a key on the SBM-01. Furthermore
settings can be made to leave the backlight always ON or
always OFF. In the setting AU the backlight will be activated
automatically when the charge/discharge current exceeds 1A
or when a key is pressed.
Default : 30 seconds
Range
Stepsize : 10 seconds
F18 : Alarm relay contact polarity. This Function enables selection
between a normally open (NO) or normally closed (NC)
contact . Please note that the NC setting will slightly increase
the SBM-01's supply current in normal operating mode.
Default : NO
Range
F19 : Firmware version. Displays the firmware version of the SBM-
01. No alterations can be made.
Default : x.xx
F20 : Setup lock. When this Function is ON, all functions (except
this one) are locked and can't be altered anymore.
Default : OFF
Range
When all the necessary changes are made and double checked in the
setup-mode, it is time to jump back to the normal operating mode by
pressing the SETUP key for three seconds. Your SBM-01 is now ready
for use!
: 1-1 / 1-5 / 1-10
: OFF / 10 – 60 / ON / AU
: NO / NC
: OFF / ON
SBM-01 high precision battery monitor