CS2 R30252.xx
from 75A to 200A
4
Installation
Before to install, make sure that the Thyristor unit have not damages.
If the product has a fault, please contact the dealer from which you
purchased the product. Verify that the product is the same thing as
ordered.
The Thyristor unit must be always mounted in vertical position to
improve air cooling on heat-sink.
Maintain the minimum distances (
represented, this area must be free from obstacle (wire, copper bar,
plastic channel).
When more unit has mounted inside the cabinet maintain the air
circulation like represented in figure without obstacle for the air flow.
Is necessary to install a fan to have better air circulation as calculated
previously.
The V Air flow must be equal or more than the value calculated.
If the cabinet fan mounted by the customer have an air flow lower
than the correct value the warranty will decay
4 1 Dimensions and Weight
W
*
) in vertical and in horizontal as
Size
H
75A (S09)
125A (S09)
150A (S09)
200A (S10)
D
15
2 cm
AIR FLOW IN (V)
W (mm)
H (mm)
116
316
116
316
116
316
120
350
User's manual
AIR FLOW OUT (V)
FAN
in aspiration
30 cm
20 cm
Air Grid
D (mm)
Weight (kg)
187
5
187
5
187
5
220
5,5