ENGLISH OPERATING INSTRUCTIONS
DS/DSN
©2019 MELTRIC Corporation. All rights reserved.
MELTRIC Corporation / 4765 W. Oakwood Park Drive Franklin, WI 53132
Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com
MARECHAL
A manufacturer of products using
meltric.com
GENERAL
DS and DSN Series products are designed to provide
the safety and functionality of a switch with the con-
venience of a plug & receptacle. They can safely be
used to make and break electrical connections and
are an approved 'line of sight' disconnect switch.
There are inherent dangers
WARNING
associated with electrical
products. Failure to follow safety precautions can result
DANGER
in serious injury or death. These instructions must be
followed to ensure the safe and proper installation, oper-
CAUTION
ation and maintenance of the MELTRIC devices. Before
installation, disconnect all sources of power to the circuit
NOTICE
to eliminate the risk of electrical shock.
ADVERTENCIA
RATINGS
DANGER
DS and DSN Series Switch Rated plugs & receptacles
are UL & CSA listed in accordance with UL 1682,
Subject 2682 and CSA 22.2 182.1. All are listed as
CAUTION
'Branch Circuit Disconnect Switches', are horsepower
rated, and listed as 'Motor Circuit Disconnect Switches'.
AVISO
The amperage, voltage, horsepower, switch, and
environmental ratings are indicated on the
product labels.
All DS/DSN devices are rated to make and withstand
short circuit currents with appropriate fusing as indi-
cated in Table 1. Some DS and DSN devices are pro-
vided with optional auxiliary contacts that make after
and break before the phase contacts. The ratings for
auxiliary contacts are shown in Table 2.
Table 1 - Short Circuit Make & Withstand Ratings
Device
Rating Fuse
10 kA @ 600 VAC
DSN20
20A
100 kA @ 600 VAC
DSN30
30A
100 kA @ 600 VAC
DSN60
60A
100 kA @ 600 VAC
10 kA @ 600 VAC
DSN150
150A
100 kA @ 600 VAC
DS20
20A
100 kA @ 600 VAC
DS30
30A
100 kA @ 600 VAC
DS60
60A
100 kA @ 600 VAC
DS100C
100A
100 kA @ 600 VAC
65 kA @ 600 VAC
DS100
100A
65 kA @ 600 VAC
10 kA @ 600 VAC
DS200
200A
65 kA @ 600 VAC
Over current protection markings DS100:
Suitable for use on a circuit capable of delivering, not more than
65kA RMS symmetrical amperes @ 600 VAC maximum.
See table 1 for maximum fuse sizing.
* Rating applies with fusing up to this amperage. Ratings are
based on tests performed with Mersen RK1 non-time delay
current limiting fuses and Mersen RK5 time delayed fuses.
Table 2 - Auxiliary Contact Ratings
Device
DSN20
DSN30, DSN60
DSN150, DS100, DS200
DS20, DS30
DS60, DS100C, 2 Aux
DS60, DS100C, 3 & 4 Aux
INSTALLATION
DS/DSN should be installed by qualified
personnel in accordance with all applicable
local and national electrical codes.
Before starting, verify that the power is off, that the
WARNING
product ratings are appropriate for the application, and
that the conductors meet code requirements and are
DANGER
within the capacities of the terminals noted in Table 3.
INSDS/DSN AF
CAUTION
Table 3 - Wiring Terminal Capacity
NOTICE
Device
®
TECHNOLOGY
ADVERTENCIA
DSN20
DSN30
DANGER
DSN60
DSN150
4
CAUTION
DS20
DS30
AVISO
DS60
DS100C
DS100
DS200
Capacity is based on THHN wire sizes
1
Auxiliary contacts are optional and may not be on all products.
2
Auxiliary contacts are prewired at the factory.
3
The DSN150 is intended to be wired with 2/0 conductors rated
4
75°C or higher at 150 amps.
General Notes & Precautions
1. Self-tapping screws are provided for use with
some polymeric accessories. High torque may
be required to drive them in. Once they are
seated, care should be taken in order to avoid
over-tightening them against the plastic material.
2. Various handles and cord grip options may be
used. These instructions are based on handles
provided with integral multi-layer bushing cord grips.
3. Wire strip lengths are indicated in Table 4. Strip
lengths for cable sheathing will depend on the
specific application. When used with handles, the
cable sheathing should extend into the handle to
ensure adequate strain relief.
Table 4 - Wire Strip Length – Dimensions A
Device
Type*
RK1
50A
DSN20
Phase
RK1
35A
DSN30
Phase
RK1
125A
Auxil.
RK1
110A
DSN60
Phase
RK1
400A
Auxil.
RK1
225A
DSN150
Phase
RK1
80A
DS20
Phase
RK1
125A
Auxil.
RK1
250A
DS30
Phase
RK1
250A
Auxil.
RK5
100A
DS60
Phase
RK1
175A
DS100C
Phase
RK1
500A
DS100
Phase
RK5
200A
DS200
Phase
The wire strip lengths noted on Table 4 are reference strip lengths
based on conductors with thinner insulation. Flexible cables with
thicker insulation may need to be stripped back further. Strip the
cable jacket back as necessary to ensure the conductor bottoms
out in the terminal.
120 VAC 240 VAC 480 VAC 600 VAC
0.60A
0.30A
-
-
6A
3A
1.50A
1.20A
1.50A
0.75A
0.37A
0.30A
6A
3A
1.50A
1.20A
6A
3A
1.50A
1.20A
3A
1.50A
0.75A
0.60A
1
(in AWG)
Aux.
Main Contacts
Contacts
2
Min
Max
Max
20A
14
12
18
3
30A
14
8
14
60A
14
4
14
150A
3
4
2/0
14
20A
14
8
14
30A
14
4
14
60A
10
2
14
3
100A
3
10
2
14
100A
3
4
2/0
14
200A
3
4
4/0
14
Receptacle
Plug/Inlet
Inches
mm
Inches
mm
1/2
13
5/8
16
7/16
10
3/4
19
7/16
10
3/4
19
3/4
18
7/8
22
7/16
10
3/4
19
1-3/16
30
1-3/16
30
7/16
10
3/4
19
7/16
10
3/4
19
3/4
18
7/8
22
7/16
10
3/4
19
15/16
24
15/16
24
15/16
24
15/16
24
1-3/16
30
1-3/16
30
1-1/2
38
1-1/2
38
4. Factory installed auxiliary wires should be
stripped as necessary to make a connection.
Table 5 - Terminal Screw Tightening Torques
Torque
Required Screwdriver or
Device/Contact
in-lbs
N-m
DSN20
Phase 8.9-10.6
1.0-1.2
3 mm or 1/8" precision tip
DSN30
Phase
15
1.7
4 mm or 3/16" precision tip
Auxil.
15
1.7
4 mm or 3/16" precision tip
DSN60
Phase
15
1.7
5 mm or 3/16" precision tip
Auxil.
15
1.7
3 mm or 1/8" precision tip
DSN150 Phase
90
10.2
4 mm or 3/16" precision tip
DS20
Phase
15
1.7
4 mm or 3/16" precision tip
Auxil.
15
1.7
5 mm or 3/16" precision tip
DS30
Phase
15
1.7
3 mm or 1/8" precision tip
Auxil.
15
1.7
DS60
Phase
48
5.4
DS100C Phase
48
5.4
DS100
Phase
90
10.2
DS200
Phase 110-133 12.5-15.0
5. Wiring terminals are spring assisted to prevent
loosening due to wire strand settlement, vibration
and thermal cycling. NOTICE: Do not over-
tighten the terminal screws. Appropriate tools
and tightening torques are indicated in Table 5.
6. Some auxiliary contacts are factory prewired.
Proper lugs should be used and lugs should be
crimped with the proper tool.
7. NOTICE: MELTRIC threaded handles come with
tapered style threads. The use of fitting seal tape
is recommended to maintain watertightness of
all NPT fittings, joints. To maintain environmental
protection use listed cord grips.
Finger Drawplate Gasket
Bushing
Finger Drawplate
Strain
Relief
Handle
Color-Coded
Compression
Gasket
Nut
Assembly for In-Line Connections
Do not overtighten terminal or self-tapping
screws. Tighten screws to the proper torque to
ensure a secure connection.
When most DS/DSN are used as in-line connectors,
WARNING
finger drawplates should be installed on both the
receptacle and plug in order for the user to more easily
DANGER
provide the leverage required to connect the device.
On the larger sized devices, (DS100, DSN150 &
CAUTION
DS200) the finger drawplates are not needed because
an easy closing mechanism is provided as standard.
NOTICE
For poly handles with strain relief, adjust the bushing
diameter to fit the cable by removing inner sections
ADVERTENCIA
of the bushing as required. Insert the bushing into the
strain relief, then insert the assembly into the handle
DANGER
and loosely install the compression nut. Insert the
cable through the handle, the thin black drawplate
CAUTION
gasket and finger drawplate (if applicable) and the
color coded gasket. Strip the cable sheath to provide
a workable wire length, being mindful that the sheath
AVISO
must extend into the handle to achieve a secure cord
grip. Then strip the individual wires to the lengths
indicated in Table 4 and twist the strands of each
conductor together.
Back out the terminal screws on the receptacle (or
inlet) far enough (but not completely) to allow the
conductors to pass, insert the conductors fully into
the proper terminals and tighten the screws with the
appropriate tool to the torque indicated in Table 5.
Verify that the cable jacket extends beyond the strain relief
and into the handle. Assemble the receptacle (or inlet), the
color coded gasket, the finger drawplate, and the thin black
drawplate gasket to the handle with the four self-tapping
screws provided. Adjust the cable location so that it will
not be under tension inside the handle and tighten the
compression nut to secure the cable.
Allen Wrench
4 mm hex head
4 mm hex head
4 mm hex head
4 mm hex head
5 mm hex head
Receptacle
(or Inlet)

Publicité

loading

Sommaire des Matières pour Meltric DS Serie

  • Page 1 5 mm hex head DS200 Phase 110-133 12.5-15.0 Aux. Main Contacts NOTICE Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com Contacts 5. Wiring terminals are spring assisted to prevent Device MARECHAL ® TECHNOLOGY...
  • Page 2 NOTICE through the hole provided in the casing. This will pre- individual wires MELTRIC plugs and receptacles can only be used in vent the plug from being inserted into a receptacle. WARNING to the lengths conjunction with mating receptacles or plugs manu-...
  • Page 3 MELTRIC Corporation / 4765 W. Oakwood Park Drive Franklin, WI 53132 qui empêchent le desserrage causé par le tassement Principal Aux. Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com NOTICE Contacts Contacts des torons métalliques, les vibrations et le cyclage thermique.
  • Page 4 Les fiches et prises MELTRIC peuvent uniquement être identiques pour conserver le même indice une fois la paire soit exercée vers le bas, en direction opposée du verrou.
  • Page 5 4 mm de cabeza hexagonal MELTRIC Corporation / 4765 W. Oakwood Park Drive Franklin, WI 53132 NOTICE Contactos Contactos Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com DS100C Fase 4 mm de cabeza hexagonal Principales...
  • Page 6 También aplica para el tomacorriente cuando El montaje con el gatillo en la parte clavijas MELTRIC y otro fabricante autorizado de los pro- superior contrarresta el peso y la DANGER la caja de conexiones la tapa está...

Ce manuel est également adapté pour:

Dsn serieDsn20Dsn30Dsn60Dsn150Ds100 ... Afficher tout