Connecting the device
Observe the admissible loads.
Observe the Technical Operating Conditions of the
power supply companies.
Do not exceed the permissible total load including
transformer losses.
Operate inductive transformers with at least 85% of
their rated load.
When mixed loads are used with inductive transform-
ers, the share of resistive loads must not exceed 50 %.
Troublefree operation is ensured only with Berker TRONIC
transformers or with inductive iron-copper transformers.
CAUTION
Risk of irreparable damage with mixed loads.
Do not connect capacitive loads (e.g. elec-
tronic transformers) and inductive loads
(e.g. conventional transformers) in common
to the same dimming output.
Connect the device as shown in the wiring example
(Fig. 3).
Delivery state: provisional operation possible, output
control via keypad enabled. Automatic selection of
dimming principle.
NL
Toestel aansluiten
Op toegestane lasten letten.
Technische aansluitvoorwaarden (TAV) van het ener-
giebedrijf in acht nemen.
Toegestane totale last inclusief trafovermogensverlies
niet overschrijden!
Inductieve trafo's met minstens 85% van de nominale
last belasten.
Menglasten met inductieve trafo's: ohmse last max. 50%.
Een probleemloze werking wordt door ons alleen bij
gebruik van Berker Tronic trafo's of inductieve ijzer-
koper-transformators gegarandeerd.
VOORZICHTIG!
Gevaar voor vernieling door menglasten!
Capacitieve lasten, bijv. elektronische tra-
fo's, en inductieve lasten, bijv. conventio-
nele trafo's, niet samen op één dimuitgang
aansluiten.
Aansluiten volgens aansluitvoorbeeld (afbeelding 3).
Toestand bij levering: Bediening van de uitgangen
via toetspaneel mogelijk, inzetbaar op bouwplaat-
sen Automatische selectie van het dimprincipe.
27

Publicité

loading