ADVANCE-GRP
An example of the label used for the certified interlocked socket is shown below:
Via Costa Erta 15 Parre BG ITALY
503.6387-F
IMQ 11 ATEX 010
Ex tb IIIC T90°C Db IP66
T90°C Ta -25 +60°C
DO NOT OPEN WHEN ENERGIZED ENCLOSURE
AND WAIT AT LEAST 15 MINUTES AFTER HAVING DISCONNECTED POWER
WARNING THE CABLE ENTRY POINT CAN BE EXCEED 85°C
Details of the adhesive label or steel plate.
READ THIS DOCUMENT CAREFULLY PRIOR TO THE INSTALLATION
Recipients: expert electricians or duly trained personnel.
1. SAFETY INFORMATION
The interlocked sockets of the ADVANCE-GRP Series are used for fixed installations in environments with a potential risk of
explosion due to the presence of combustible dust classified as Zone 21.
These installation, use and maintenance instructions must be kept in a safe place for future reference. During operation or
maintenance jobs on the device, do not leave this manual or other objects inside the enclosure.
Use the ADVANCE-GRP Series interlocked sockets for their approved use only, and keep them fully intact and perfectly clean. The
interlocked sockets have been designed to withstand shocks of 7J, and to be used under normal vibration conditions.
They have not been designed for use in environments subject to extreme vibrations. The enclosure is made of fibreglass-
reinforced polyester.
The type of protection cannot be guaranteed if the product is not installed correctly.
Use only original spare parts supplied by SCAME.
No modification/work is allowed on the interlocked socket unless specifically indicated in this manual.
DO NOT OPEN THE ENERGIZED ENCLOSURE IN PRESENCE OF AN EXPLOSIVE ATMOSPHERE.
Always comply with national accident-prevention rules and with the safety instructions contained in this manual whenever
you work on the interlocked socket.
Rated current
Built-in control and/or protection device
SCAME Command Series
switch-disconnector
Command and relevant fuses 16-32A:
10:3 38 gG - 63A : CH 22 X 58 63A gG
Ground terminal
Technical data, connection capacities of the terminals and tightening torques.
MP36510
2012
3P+N+
63A - 6h
346-415V~
0051
II 2D
503.16...F
503.32...F
503.63...F
-
16A
Power supply terminals -
Code
Tightening torque (Nm)
503.16...
503.32...
0,8
503.63...
0,8
503.16....
503.32....
1,2
503.63....
11
32A
63A
0,8
3,6
0,8
3,6
1,2
3,5