Daisy Chain Wiring; Setting The Communication Speed; Assigning Id Numbers - Aerotech RELAY PANEL CS Guide D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

RELAY PANEL CS
EN
4.4.. Daisy.Chain.Wiring
Be sure to make linear connections between
the modules. Do not make star connections,
this type of connection can cause communi-
cation errors.
DO NOT make star connections when
connecting the relays panels!
4.5.. Setting.the.Communi-
cation.Speed
ON
OFF
The 8
switch of the switch blocks is re-
th
served to set the com muni cation speed
(see picture 4). Select the high-speed mode
(internal switch #8=ON) if all devices on the
communication line are compatible with the
high-speed mode or select the regular speed
(internal switch #8=OFF) if 1 device on the
communication line does not support the
high-speed mode.
*This note does not apply to the
internal switches of the variable-output board.
The high speed mode is only available
on some models of environment control.
Let the 8
switch OFF if your controller
th
does not have this capability.
If many internal switches are located
behind the top cover of your relay panel
or if you are using several panels, make
sure all switches #8 have the same posi-
tion.
*This note does not apply to the internal
switches of the variable-output board.
4.6.. Assigning.ID.Numbers
ON
OFF
A relay panel can have up to 3 electronic
boards located behind its front door and one
optional variable-output board located in
the bottom of the enclosure (see picture 4).
Each of these boards must be given a unique
identification number so that the environment
control can communicate with it properly.
Use dipswitches #1-7 to assign the ID number
of each board. The table on the right shows
how to set the switches for each possible ID
number. Refer to the wiring diagram of your
particular controller to see what ID number
must be given to each relay board of your
relay panel.
4
RELAY PANEL CS rev.05
Relay Panel CS
Relay Panel CS
SWITCH NUMBER
1
2
3
4
5
ID 1
ID 2
ON
ID 3
ON
ID 4
ON
ON
ID 5
ON
ID 6
ON
ON
ID 7
ON
ON
ID 8
ON
ON
ON
ID 9
ON
ID 10
ON
ON
ID 11
ON
ON
ID 12
ON
ON
ON
ID 13
ON
ON
ID 14
ON
ON
ON
ID 15
ON
ON
ON
ID 16
ON
ON
ON
ON
ID 17
ON
ID 18
ON
ON
ID 19
ON
ON
ID 20
ON
ON
ON
ID 21
ON
ON
ID 22
ON
ON
ON
ID 23
ON
ON
ON
ID 24
ON
ON
ON
ON
ID 25
ON
ON
ID 26
ON
ON
ON
ID 27
ON
ON
ON
ID 28
ON
ON
ON
ON
ID 29
ON
ON
ON
ID 30
ON
ON
ON
ON
ID 31
ON
ON
ON
ON
ID 32
ON
ON
ON
ON
ON
OK
Linear Wiring
(Correct)
Relay Panel CS
Star Connection
(not correct)
Figure 7. Communication Wiring Do & Don't
6
7
8
1
Reserved
ID 33
ID 34
ON
ID 35
ON
ID 36
ON
ON
ID 37
ID 38
ON
ID 39
ON
ID 40
ON
ON
ID 41
ID 42
ON
ID 43
ON
ID 44
ON
ON
ID 45
ID 46
ON
ID 47
ON
ID 48
ON
ON
ID 49
ID 50
ON
ID 51
ON
ID 52
ON
ON
ID 53
ID 54
ON
ID 55
ON
ID 56
ON
ON
ID 57
ID 58
ON
ID 59
ON
ID 60
ON
ON
ID 61
ID 62
ON
ID 63
ON
ID 64
ON
ON
From
Controller
From
Controller
SWITCH NUMBER
2
3
4
5
6
7
8
Reserved
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Figure 6. ID Switch Positions