2.0 FRAMING AND CLEARANCES
2.1 Clearance to Sprinkler
•
In a situation where a sprinkler head is installed within the
proximity to a #KZK discharge opening, the diagram below
MUST be followed.
•
The distance between a sprinkler head and discharge opening
cannot be less than 60" (1524mm) in length at every point from
the origin of the discharge opening. You must also verify the
sprinkler head sensor is set to the proper heat setting so it does
not activate when the room heats up from the fireplace being
operated normally.
•
Please follow local building codes to determine what
temperature setting is relevant for your installation.
CEILING
SPRINKLER HEAD
Figure 2.1, KZK Clearance to Sprinkler
Komfort Zone Kit #KZK-050
60"
(1524mm) MIN
½
2
"
(63mm)
MIN
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
7