18. Wiring diagrams
Disconnect the line and the supply when operating on terminals.
THREE-PHASE STANDARD CONNECTION (default) Default wiring configuration for standard applications.
Voltage measure
Current measure
Phase angle offset
Capacitor overload current measure
Parameter setting
• For three-phase connection, the voltage input must be connected phase to phase; the current transformer must be connected on the
remaining phase.
The polarity of the current/voltage input is indifferent.
•
WARNING!
Standard Three-phase wiring
NOTES
1 ph-to-ph voltage reading L2-L3
L1 phase
Between V (L2-L3 ) and I (L1)
1 reading calculated on L2-L3
P.03 = L1
P.05 = L2-L3
P.24 = 3PH
90°