ND 5119-5 61-065 Vol-Con Ins
#61-065
Voltage Tester
Instruction Manual
WARNING
Read First: Safety Information
Use the tester only as specified in this manual;
otherwise, the protection provided by the tester
may be impaired.
Warning
To avoid possible electric shock or personal
injury, follow these guidelines:
• Do not use tester if it is damaged. Visually
inspect tester to ensure case is not cracked.
• Inspect and replace leads if insulation is
damaged, metal is exposed, or probes are
cracked. Pay particular attention to the
insulation surrounding the connectors.
• Do not use tester if it operates abnormally as
protection maybe impaired.
• Do not use during electrical storms or in wet
weather.
• Do not use around explosive gas, dust, or vapor.
• Do not apply more than the rated voltage to
the tester. Voltage is not to exceed 600V.
• Always operate this solenoid-type tester
within the specified duty cycle on the front of
the tester. Duty cycle ratio is:
• 1:7 ON:OFF time for 240V or less
• 1:40 ON:OFF time for 240V or greater.
• Maximum ON time is 15 seconds.
Caution
To protect yourself, think "Safety First":
• Voltages exceeding 30VAC or 60VDC pose
a shock hazard so use caution.
• Never ground yourself when taking electrical
measurements.
2/19/07
9:18 AM
Page 1
• Use appropriate personal protective equipment
such as safety glasses, face shields, insulating
gloves, insulating boots, and/or insulating
mats.
• Use the 3-Step Testing Method. Before each
use:
• Verify tester operation by measuring a
known voltage. Apply tester to circuit under
test. And, then test on the known live volt-
age again to ensure proper operation.
• Connect the black common lead to ground
before applying the red test lead to voltage.
Disconnect the red test lead from the volt-
age first.
• Always work with a partner.
• When using the probes, keep fingers as far
behind the probe tips as possible.
Features:
• Vibration Mode with indicator movement
• Independent solenoid and electronic circuitry
design provides back-up voltage indication
for added safety
• Low Impedance Measuring Device
• Replaceable Test Leads
• Shielded probe tips
• Ultrasonically welded for added durability
Accessories:
• 61-072 Resistor-fused test leads
• C-90 Soft-sided carrying case
• 61-010 Leather case
To Measure AC Voltage:
• Ensure that the plug for the test leads is fully
seated into the banana jacks.
• Connect the tester in parallel with the load or
circuit.
• The tester indicates both the voltage type and
the voltage level.
To Measure DC Voltage:
• Ensure that the plug for the test leads is fully
seated into the banana jacks.
• Connect the tester in parallel with the load or
circuit.
• The tester indicates the voltage type, polarity,
and the voltage level.
2

Publicité

loading

Sommaire des Matières pour IDEAL 61-065

  • Page 1 ND 5119-5 61-065 Vol-Con Ins 2/19/07 9:18 AM Page 1 #61-065 • Use appropriate personal protective equipment such as safety glasses, face shields, insulating gloves, insulating boots, and/or insulating mats. • Use the 3-Step Testing Method. Before each Voltage Tester...
  • Page 2 Operating Environment: 32° F to 122° F Test Lead Replacement: (<70% humidity) • Replace leads only with IDEAL test leads Storage Temp.: -4° F to 140° F below. (<80% humidity) • # 61-070 Standard Test Leads with...
  • Page 3 This tester is warranted to the original purchaser against defects in material and workmanship for five years after purchase. During this warranty period, IDEAL INDUSTRIES, INC. will, at it’ s Probador de voltaje test option, replace or repair the defective unit, sub- Manual de instrucciones ject to verification of the defect or malfunction.
  • Page 4 ND 5119-5 61-065 Vol-Con Ins 2/19/07 9:18 AM Page 7 Precaución Para medir el voltaje de CA: Para protegerse, piense en la "Seguridad ante • Asegúrese de que el enchufe de los cables todo": de prueba esté completamente asentado en •...
  • Page 5 Piezas de servicio y repuesto: Cualquier garantía implícita que sea consecuen- Para obtener piezas de repuesto o preguntar sobre cia de la venta de un producto IDEAL se limita a contactos de información de servicio. lo de arriba, pero no se limita a garantías IDEAL INDUSTRIES, INC.
  • Page 6 ND 5119-5 61-065 Vol-Con Ins 2/19/07 9:18 AM Page 11 #61-065 • 1:7 délai ACTIF:INACTIF pour 240 V ou moins. • 1:40 délai ACTIF:INACTIF pour 240 V ou plus. • Le délai ACTIF maximum est de 15 sec- ondes. Testeur de tension Attention Mode d’emploi...
  • Page 7 ND 5119-5 61-065 Vol-Con Ins 2/19/07 9:18 AM Page 13 • Dispositif de mesure à faible impédance • Test de fréquence de 25 à 60 Hz • Conducteurs d’essai remplaçables Placer un testeur entre les deux côtés d’une • Pointes de sondes protégées ligne c.a.
  • Page 8 V c.a. valeur efficace. Toutes les garanties implicites résultant de la Environnement de fonctionnement : 0° à 50° C vente d'un produit IDEAL, y compris, mais non (32° F à 122° F) de façon limitative, les garanties de valeur (<...