8. Adjustment of zero point / span / 9. Maintenance, accessories
PEX10, PEX11, PEX15:
A
Make sure wires are not cut or pinche during disassembly and reassembly of the connector.
PEX10, PEX11, PEX15: Remove the female connector. Open the pressure sensor by detaching
the clamping nut (see Fig. A ). Carefully remove the male connector from the case.
PEX13, PEX14, PEX15 with field case: Open the pressure sensor by twisting off the fied case over.
Adjust the zero point (Z) (see Fig. B ) by generating the lower limit of the pressure range.
Adjust the span (S) by generating the higher limit of the pressure range.
Check the zero point.
If the zero point is incorrect, repeat procedure as required.
Reassemble the instrument carefully.
Make sure all sealings and o-rings are not damaged and correctly installed to assure the
rated moisture ingress protection.
Recommended recalibration cycle: 1 year
9. Maintenance, accessories
tecsis pressure sensors require no maintenance.
Have repairs performed by the manufacturer only.
40