Parameter
Parame-
ter Code
Name
Wired controller
C0
Two-pipe/four-pipe
C1
selection
ECO cooling temperature
C2
ECO heating
C3
temperature setting
C4
Anti-freezing protection
Anti-freeze temperature
C5
C6
Baud rate setting
C7
Celsius/Fahrenheit
C8
Button backlight setting
C9
Language
Cooling/Fan temperature
C10
compensation
Heating/Auxiliary electric
C11
heater temperature
compensation
Temperature return
C12
difference
Fan always on/always off
C13
(After setting temperature)
Note: Items marked with " " are functions that are not supported if
non-networked.
Parameter Range
01-32
address
00: Two-pipe cooling and heating
01: Two-pipe cooling
02: Two-pipe cooling + Auxiliary
electric heater
03: Two-pipe heating + Auxiliary
electric heater
04: Two-pipe cooling and heating +
Auxiliary electric heater
05: Four-pipe
17°C to 30°C / 62°F to 86°F
setting
17°C to 30°C / 62°F to 86°F
00: Off
0°C to 20°C / 32°F to 68°F
setting
00: 4800
00: °C
00: Off
00: Chinese
-10°C to 10°C / -18°F to 18°F
-10°C to 10°C / -18°F to 18°F
1, 2, 3 (°C) / 2, 4, 6 (°F)
00: Always on
Default
26°C /79°F
18°C /64°F
01: Start
5°C / 41°F
01: 9600
01: °F
01: On
01: English
0°C / 0°F
0°C / 0°F
1°C / 2°F
01: Always off0
09
Remarks
Value
01
00
Stepping 0.5°C /1°F
Stepping 0.5°C /1°F
00
Stepping 0.5°C /1°F
01
00
01
01
Stepping 0.5°C /1°F
Stepping 0.5°C /1°F