• F ollow the instructions for the smoke detector when determining the
installation location. Install the radio modules on the ceiling. The radio
range is greatest in the direction of the marking on the housing of the radio
module (Fig. 7).
• P lug the three-pin terminal of the radio module (Fig. 1.3) onto the underside
of the smoke detector (Fig. 2).
• P ut the smoke detector onto the installed radio module and carefully
turn the smoke detector in a clockwise direction until it locks into place.
During this process, the marking on the housing of the radio module
and the marking on the housing of the smoke detector must align
with each another (Fig. 7). If a battery is not inserted into the smoke
detector, it is not possible to lock the smoke detector in place on the
radio module.
Note: Make sure that the connection wires are not routed over
the circuit board of the radio module — instead, they must be
routed directly from the edge of the housing to the three-pin plug
on the radio module
• O nce all radio modules/smoke detectors are installed, perform a
function test by pressing the test button on the smoke detector until
the smoke detector emits three alarm sounds. When performing the
function test, follow the instructions for the smoke detector. The radio
modules/smoke detectors of the same radio group signal the alarm
acoustically and automatically return to normal mode after a short
period of time. If a detector forwards the OUT signal, it acknowledges
that it has done so by emitting three short sounds. See the section
entitled „Operation/testing".
The device is approved for operation inside the European Community.
GEV GmbH hereby declares that this device (Radio Transmit and Receive
Module FMF 3545) accords with the fundamental requirements and the
other relevant regulations of guideline 1999/5EG. The full declaration of
conformity can be seen under: www.gev.de
Recycling guidelines:
This device must not be disposed of as unsorted household waste.
Used devices must be disposed of correctly. Contact your local town
council for more information.
Technical data:
Type designation
Frequency
Operating voltage
Working temperature range
Relative humidity
Dimensions
Colour
Technical and design features may be subject to change.
GEV GmbH
Fax: +49 (0)180/59 58 555
Heidenhofweg 16
www.gev.de
25499 Tangstedt
service@gev.de
Germany
10
FMF 3545
0–868 MHz
9V from the smoke detector
0–40°C
0–90% non-condensing
Ø 106 mm, height 12 mm
white