HOLDING REGISTERS (Read / write)
Data type
40001 Device slave
unsigned int.
address
40002 Modbus baud rate
unsigned int.
40003 Modbus parity
unsigned int.
mode
40004 Device type
unsigned int.
40005 HW version
unsigned int.
40006 FW version
unsigned int.
40007-
40008
40009 Steps
unsigned int.
40010 Start step
unsigned int.
40011 Minimum output
unsigned int.
value
40012 Maximum output
unsigned int.
value
40013 Overwrite mode
unsigned int.
40014 Overwrite value
unsigned int.
40015 Output mode
unsigned int.
40016 PWM output
unsigned int.
40017 Run / Stand-by
unsigned int.
40018 Start output value
unsigned int.
40019
Network Bus
40020
Termination
unsigned int.
Resistor (NBT )
Note: Les registres de maintien (HOLDING) peuvent êtregérés via les commandes Modbus suivantes "Read Holding Registers", "Write Single Register" ou "Write Multiple Registers".
Pour en savoir plus à propos de Modbus sur liaison série, s'il vous plaît visitez:
MIW-RDCV-FR-003 - 28 / 07 / 17
Description
Modbus device address
Modbus communication baud rate
Modbus parity check mode
Device type (read-only)
Hardware version of the device (read-only)
Firmware version of the device (read-only)
Reserved, return 0
Starting step. Active when the number of the steps (40009) > 0
Starting step
Sets the minimum value of output signal
Sets the maximum value of output signal
Selection of overwrite mode.
Output value in overwrite mode in %
Selection of the output mode: Voltage / Current / PWM
Selection of the PWM output type: Open collector (OC) /
Pull-up +12 VDC.
Selection of Run / Stand-by mode
Start value of the output signal. Active when steps number (40009) = 0.
Reserved, returns 0
Sets the unit as first or last unit on the line by connecting NBT resistor
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
Retour à la Table des matières
Data
1—247
0—6
0—2
2300
XXXX
XXXX
0—9
0—9
0—80
20—100
0—1
0—100
0—2
0—1
0—1
0—100
0—1
www.atib.fr
Mode manuel
Default
Values
1
0 =
1 =
2 =
2
3 =
4 =
5 =
6 =
0 =
1
1 =
2 =
2300 =
0 x 0100 =
HW version 1.0
0 x 0300 =
FW version 3.0
0 =
0
1 =
2 steps: Min / Max
9 =
0 =
Start at the first step
0
1 =
Start at the second step
20
20 =
2 VDC / 4 mA / 20 % PWM
100
80 = 8 VDC / 16 mA / 80 % PWM
0 =
0
1 =
50
50 =
0 =
0
1 =
2 =
0 =
Open collector
0
1 =
Pull-up +12 VDC
0 =
0
1 =
20
20 =
2 VDC / 4 mA / 20 % PWM
0 =
Disconnected (NBT open)
0
1 =
Connected (NBT closed)
4.800
9.600
19.200
38.400
57.600
115.200
230.400
8N1
8E1
8O1
RDCV9-AD
1 % per step
10 steps
Inactive
Active
50 %
0—10 VDC
0—20 mA
PWM
Run
Stand-by