EPO (Emergency Power Off) Option
The output power can be disabled in an emergency by closing a switch connected to the EPO.
Adhere to national and local electrical codes when wiring.
Rockwell Automation recommends Allen-Bradley Catalog Number 800F Emergency Stop Operator as the interface to the EPO
to connector.
The switch should be connected in a normally open switch contact. External voltage is not required; the switch is driven by
12 V internal supply. In closed condition, 2m A of current are drawn.
The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.
The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and an SELV circuit (IEC standard).
Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal
block unless it can be confirmed that the circuit is Class 2 or SELV.
If circuit standard cannot be confirmed, use a contact closure switch.
Use one of the following cable types to connect the UPS to the EPO switch:
CL2: Class 2 cable for general use.
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
CLEX: Limited use cable for use in dwellings and for use in raceways.
For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).
For installation in other countries: Use standard low-voltage cable in accordance with local regulations.
M
AINTENANCE AND
Installing and Replacing the Battery Module(s)
This UPS has easy to replace, hot-swappable battery modules. Replacement is a safe procedure, isolated from electrical hazards.
You may leave the UPS and connected equipment on during the procedure.
Refer to the Bulletin 1609-P UPS Information CD for more details.
Troubleshooting
Refer to the user manual on the Bulletin 1609-P UPS Information CD for details.
Allen-Bradley Company, LLC
Industrial Components Business
1201 South Second Street
Milwaukee, WI 53204-2496 USA
Phone 440.646.5800
www.ab.com
41063-258-01 (1)
T
ROUBLESHOOTING
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

1609-p10000e

Table des Matières