PERATION
Indicator
Description
The UPS is drawing utility power and performing double conversion to supply power to connected equipment
Online
(see Troubleshooting).
The UPS is supplying battery power to the connected equipment.
On Battery
The UPS is in bypass mode, sending utility power directly to connected equipment.
Bypass
Bypass mode operation is the result of an internal UPS fault, an overload condition or a user initiated command
either through an accessory or the manual bypass switch. Battery operation is not available while the UPS is in
bypass mode (see Troubleshooting).
The UPS detects an internal fault (see Troubleshooting).
Fault
The connected loads are drawing more power than the UPS power rating (see Troubleshooting).
Overload
The battery is disconnected or must be replaced (see Troubleshooting).
Replace
Battery
Feature
Function
Press this button to turn on the UPS. (Read on for additional capabilities.)
Power On
Press this button to turn off the UPS.
Power Off
Manually switch connected equipment to bypass mode, so that utility power is sent directly to connected
Normal /
Bypass
equipment. Battery operation is not available while the UPS is in bypass mode. (See Troubleshooting.)
This is not a normal condition.
Cold Start
Supply immediate battery power to the UPS and connected equipment (see Troubleshooting). Press and hold
the
second beep, release the button.
Automatic: The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by
Self-Test
default). During the self-test, the UPS briefly operates the connected equipment on battery.
Manual: Press and hold the
F
button to power up the UPS and connected equipment. The UPS will emit two beeps. During the
button for a few seconds to initiate the self-test.
5