Mounting instructions

Positioning
In main living room, on an inside wall: not exposed to
sun or other foreign heat sources (chimny wall, near
radiators, draughts, televisions, lamps); not hidden
by furniture, or curtains; ca. 1.2-1.5m above the floor;
due to draughts seal installation conduit.
Dimensions
-
+
8
85
The housing floor can be used as a stencil for boring
holes.
The cover can be opened by depressing
the strap with a screwdriver (on the right
side of the wall, in the middle).
Installation
Allowable cable length is max. 200m for > 1.0mm
wire (total length of all cables). Avoid running the cable
parallel to the main (230VAC) power supply cable
(electrical disturbances/protective insulation). If
possible use a 2 wire cable (not two individual wires).
Avoid conduit- or connector-box.
Commissioning (Address setting)
Connect the remote control with
the controller (see diagram
ADR
below). The address for the
0
remote control is set on the
back of the unit. This must cor-
respond with the address from the heating circuit
(important for systems with multiple heating circuits).
Factory setting: 1
Hint:
If a room sensor is connected and is used in the
controller, do not install a thermal valve in the
reference room.
RFB511A
Scheme
RFB511A
7 20