Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Switch on the power and make sure that the red indicator LEDS are in the following condition:
- L1
Red power on LED
- L2
Red LED for the time programming button
- L3
Red security LED for the blocking button "TB"
- L4
Red security LED for the inverting photoelectric cells "FTCI"
- L5
Red security LED for the stop photoelectric cells "FTCI"
Check that the activation of the safety devices (those that have not been bridged) switch the corre-
sponding LEDS off.
If the red power on LED "L1" doesn't light up check the condition of the fuses and the power cable con-
nection between binding posts "4" and "5" (fig. 1).
If one or more of the safety LEDS do not light up, check the contacts of the relative security devices and
check that the unused safety device contacts have been bridged.
TIME PROGRAMMING PROCEDURE
Work time:
The barrier is considered completely open (and therefore automatic reclosing is carried out)
even when the opening time has ended (and the FCA travel limit has not intervened); program
the opening times so as to leave a margin greater than the time required to reach the opening
travel limit FCA.
Pause time:
Set the pause time according to the characteristics of the motor; if that time is very brief the
gate will carry out a rapid travel direction inversion as soon as it reached the completely open
position.
You are advised to set a time of 5 seconds for a 6 metre boom

JUMPER SETTINGS

To set the dip-switches; turn off the power to the programmer, change the settings
and then switch the power back on.
J1:
Closed => closing command is activated when the "TC" contact closes.
Open
=> closing command is activated when the "TC" contact opens.
J2:
Closed => warning light output continuously activated.
Open
=> warning light output intermittently activated.
"CLOSING MEMORY" SETTING
It is possible to force the programmer to make the bar close again (if it can't detect the closing
travel limit "FCC") when the power has returned after a blackout.
The reclosing function (only in this situation) is preceded by the warning lights flashing for 3
seconds.
To select this function you must set DIP1 to the "ON" position before programming the
system. Setting DIP1 to the "OFF" position disables this function.
After you have finished programming you may use the dip-switch to select the automatic/semi-
automatic function and thereafter you can change from one selection to the other without effect-
ing the "closing memory" setting (which can only be set during the programming cycle).
WORK TIME PROGRAMMING (OPENING AND PAUSE)
If the bar is not completely closed (and therefore "FCC" is not active) pressing the "P1" button
will force a 15 second closing manoeuvre; repeat the manoeuvre until "FCC" is fully closed. You
may then proceed with programming.
1. With the barrier completely closed, press and hold down the "P1" button for 4 seconds. Led
"L2" will be off to start with and will then start to flash rapidly indicating that the program-
ming mode has been entered. The "POSFCC" output (on the optional card "MRS") will be
switched to "intermittent output" at the same frequency as that of the led "L2".
11
on
off
on
on
on
0-60 seconds
0-120 seconds

Publicité

Table des Matières
loading

Table des Matières