Installation and operating manual
Wired input din rail receiver with radio control switch
Réf. 10020093
1. General
1.1 Use
The wired input din rail receiver with radio control switch
radio signals from switch transmitters, or sensors (see compatibility table §6.1), a connection
with wired push button, while increasing the scope if necessary (see §6.4) between transmitters
0
LINE
and other receivers
2
. Associated as sensor (see §5.2) on BMS products, one can get an
acknowledgment to each change or an access to advanced functions such as radio test function
(see §6.3). It is used for switching loads, e.g. incandescent, halogen, fluorescent tubes, halogen
lamps with TBT ferromagnetic transformer and electronic, power contactor or small motors.
Before any use, the transmitters must be allocated to a receiver. Each sensor or transmitter can
control an unlimited number of receivers.
Note: Read the operating manual carefully before initial use.
1.2 Guarantee terms
This operating manual is an integral part of the device and our guarantee terms. It must always
be delivered to the user. We reserve the right to modify the technical design of these devices
0
TRI
SYS
without warning.
products are manufactured and their quality checked by making use
2
of the latest technologies and taking into account the applicable national and international
directives. If nevertheless a fault arises,
without prejudicing the rights of the end customer that arise from the sales contract with his
reseller.
If the event of exercising of a legitimate and regular right,
rectify the device fault or supply a fault-free device. Any claim beyond this and all claims for
consequential damages are excluded.
A legitimate fault exists if the device cannot be used at the time of delivery to the end customer
because of a design or manufacturing defect or if its practical use is severely limited. The
guarantee is void in cases of natural wear and tear, incorrect use, incorrect connection, where
the device has been repaired or external influence. The guarantee period is 24 months (from the
date of invoicing). French law applies to the regulation of guarantee rights.
1.3 Recycling of the device
To recycle the device, conform to the legislation and standards in force in the country of use.
2. Safety
WARNING! Risk of electric shocks! (See UTE C18-510) The device contains live
internal components. Risk of wounds or injuries if contact occurs! All work on
the mains supply network and the device must only be carried out by authorised
professional technicians.
• Before carrying out any work, switch-off and isolate the device.
• Secure the device to prevent it being switched back on.
• Check the device is in a zero-volts state.
• Carefully reclose the casing before reconnecting to mains power.
Observe the following points:
• The laws, standards and directives in force.
• Best practice at the time of installation.
• The device operating manual.
• An operating manual can only give general instructions. They must be interpreted in the context
of a specific installation.
The device is intended solely for use conforming to its purpose. Any repairs or modifications by
the user are forbidden! Do not use with other devices the operation of which could endanger
people, animals or property.
3. Technical characteristics
General characteristics
Transmission frequency
Category receiver
EnOcean Equipment Profile
Power supply
Terminal capacity
Output (zero potential)
1 contact micro distance (µ) opening
contact, I
=100mA
min
Ambient temperature
Storage temperature
Ambient humidity
Degree of protection
Installation altitude
Range in buildings
Masonry
20m, through 3 walls at most
Reinforced concrete
10m, through 1 wall/ceiling at most
Plasterboard / wood
30m, through 5 walls at most
Remarque: The signal strength between the transmitter and the receiver decreases as the
distance increases. Where there is a line of sight connection, the range is approximately 30m in
corridors and 100 m in large workshops or halls.
0
LINE
The range can be increased with a
2
4. Installation and initial use
4.1 Safety instructions
The installation and initial use must only be performed by authorised qualified electricians. The
electrical installation must be placed off-load before connection it to the mains (230V~/50Hz).
Conform to the legislation and standards in force in the country of use.
4.2 Installation
• This product is designed for indoor use. It is maintenance free.
• This product is intended for installation only on horizontal DIN rail, in an electrical panel
(mounted on a vertical wall) with compulsory installation of a plastron which will be connected to
the ground of the installation if it is metallic.
• For compliance with the standard reference, height of the plastron (compared to the above
DIN rail) must not exceed 48mm with a minimum thickness of 1mm.
TOC1605NUab_1116
EN
0
LINE
10020093 is used to receive
2
0
TRI
SYS
2
undertakes to remedy the default as follows,
0
TRI
SYS
2
, may at its sole discretion,
868,3 MHZ
2
D2-01-01
230V
/ 50 Hz
2
2
1x1,5
à 2,5
max rigid
max µ10A/2300VA resistive (cos φ=1)
800W incandescent/halogen
300W inductive (cos φ= 0,4 à 0,6)
/
500W/800W TBT halogen
600W fluorescent
(Uncompensated)
from -10°C to +45°C
from -20°C to +80°C
from 0 to 75%hr
(without condensation)
IP20 with plastron
2000m max.
.
repeater
• NEVER install the receiver in a metal casing or in the immediate vicinity of large metallic
objects.
• Installation on the ground or close to the ground is not recommended. Thank you to refer to
the installation standards of each country.
• Although NO output is internally connected, to the upper power to 400W it is obligatory to link
externally.
• Protect the supply line with a circuit breaker 2A curve C adapted to the installation place.
• For the controlled power over 400W, the output contact must be supplied with the same supply
line as the product, but protected separately with a circuit breaker 10A curve C adapted to the
installation place.
Connection drawing for a
lighting application ≤ 400W :
L
N
C2A
4.3 Initial use
• Connect power to the electrical installation after it has been installed.
• Program the transmitter on the receiver (see § 5), or as sensor (see §5.2) on BMS product or
diagnostic product (see §6.3).
5. Programming
For programming the receiver must be connected to the mains. The programming is conserved
during a power failure.
A small insulated screwdriver shall be used on the unit to activate the LRN or CLR buttons.
5.1 Programming mode or transmitter deletion mode
N.B.! A transmitter must not be further away than 5 m from receiver in learn mode. The
receiver has a limited range !
To enter the programming mode, short press (approximately 0,5s) the LRN button. This mode is
confirmed by the regular flashing of LED.
a) To associate a transmitter simply press on one of the switches or press the LRN button
(see §6.2). The receiver will acknowledge its recording in memory by maintaining the LED on for
4 seconds. As soon as flashing LED starts again, another transmitter can be associated or
cleared.
b) To clear a transmitter simply press on one of the switches or press the LRN button of the
desired sensor (see §6.2). The receiver will acknowledge its clearing off the memory by
maintaining the LED off for 4 seconds. As soon as flashing LED starts again, another transmitter
can be associated or cleared.
c) The transmitter association or deleting, may also be performed through the UTE
(Universal TEach-in) of EnOcean.
To exit programming mode, short press (approximately 0.5s) the LRN button. The output is
confirmed by the stopping of regular flashing of the LED.
Notes :
– No transmitter is programmed in the receiver as supplied state.
– When using BMS products, mono or multi-channel, programming must be performed alone
and channel by channel: you must exit the programming mode between each channel, by short
press the LRN button and within 5 seconds after the start of LED acquittal.
– Up to 32 switch, transmitters and sensors can be allocated to each channel.
– If the memory is full, the receiver exits programming mode upon an additional association
7mm
attempt.
– The transmitters are alternatively programmed or cleared in the event of several activations!
This also applies to wired pushbuttons.
– For transmitter of EEP 4BS type, a programming acknowledgment frame (4BS Teach-in
1
variation 3
) is always sent.
– If no button is pressed, learn mode stop automatically after 30 s.
5.2 Sensor mode
0
The receiver
acknowledgment to each change of output state. In addition, advanced features such as
querying and change of remote state become available under the profil EEP D2-01-01
a) Enable on the BMS Product in the programming mode (see the instructions).
b) Short press (approximately 0,5s) the LRN button (product 10020093) for send association
1
frames of UTE
the LED until the exit of this mode by a short press (approximately 0.5s) on the LRN button; the
output is confirmed by the stopping of regular flashing of the LED.
c) The association with this BMS product is validated upon receipt of a positive response of
1
UTE
type. This is confirmed, on the receiver, by maintaining the LED on for 4 seconds.
5.3 Clearing off all the programmed transmitters
Press the CLR button for approximately 2s. Clearing is confirmed by the regular flashing of LED.
The receiver returns automatically to programming mode.
To exit programming mode, short press (approximately 0,5s) the LRN button. The output is
confirmed by the stopping of regular flashing of the LED.
1
frame description is described in the EnOcean Equipment Profiles EEP2.6 document available
on :
www.enocean-alliance.org/en/enocean_standard
Connection drawing for a resistive
load application ≤ 2300W :
L
LN : Mains
230V~ / 50 Hz
N
Output NO :
- load disconnected when off
Gate C :
- power contacts
Note :
- The two NO terminals are
internally connected
- See section 6.2 for
Changeover of state/
Operating
LINE
10020093 once associated with a BMS product, transmits an
2
type. These emissions, every 3 seconds are indicated by the regular flashing of
C2A
Pushbutton
Wired connection
Max 100m, LED
option Max 5x0,15mA
LED display
Output status
Programming
CLR button
Cancels all
transmitters
LRN button
Learn mode
Load
C10A
1
protocol
1
:
3/4