10.1
Electrical
Characteristic values:
Resistances for simulation
of insulation resistance on 2 MΩ // 5 µF circuit
Resistances for simulation
of insulation resistance on central socket
Resistances for simulation
of insulation resistance on right-hand socket
Impedance of PE conductor
Resistances for earth and resistivity measurement
Leakage current
10.2
Dimensions and weight
Case: 490 x 395 x 195 mm
Packaging: 800 x 600 x 300 mm
10.3
Power supply
207...250 V 50/60 Hz
Mains fuse: 1.6 A 250 V (or 380 V) type FF 5 x 20 HPC
1 and 10 Ω resistances protected by a 16 A differential switch and the main fuse
Resistances of 100 to 4700 Ω protected by thermistor
Instantaneous power available: 400 VA
10.4
Environmental conditions
Temperature
- Operation: +5°C...+40°C
- Storage: -20°C...+70°C
Indoor use
Watertightness (as per EN 60529, ed. 92) :
- protection index IP 20B (open)
- protection index IP 40 (closed)
10.5
Compliance with standards
Electrical safety (according to low-voltage directive)
- Class-I instrument
- Installation category: II
- Pollution level: 2
- Rated voltage: relative to earth: 230 V
- Dielectric test voltage: 1350 V
10. TECHNICAL SPECIFICATIONS
C = 5 µF ±10%
R = 2 MΩ ±5%
Maximum voltage: 1200 V DC
Between L and N: R = 0.99 MΩ ±5%
Between L and PE: R = 26.8 MΩ ±5%
Between N and PE: R = 26.8 MΩ ±5%
Maximum voltage: 1200 V DC
R = 6.3 kΩ ±5% + 47 kΩ ±10%
Maximum voltage: 250 V AC
R = 0 Ω +0.2 Ω
R = 0,5 Ω ±0,3 Ω
R = 1 Ω ±0,3 Ω
R = 5 Ω ±10%
Imax : 1,6 A / 200 ms
R = 1 Ω, 10 Ω, 100 Ω, 1000 Ω, 1800 Ω, 2200 Ω, 4700 Ω (depending on
earth) ±20%
Approx. 4 to 34 mA with 230 V AC
10 kg
50 Hz
rms
L = 2 mH ± ± ± ± ± 10%
L = 1 mH ± ± ± ± ± 10%
L = 0,2 mH ± ± ± ± ± 10%
26