Humidity sensor Error (only on +14°C/+16°C units)
In the event that the humidity sensor is broken or its connection is interrupted on the
display the label [E5], is visualised; the humidity control device is automatically
deactivated.
UNIT WITH BROKEN SENSOR PROBES DURING DEFROST
Room probe error
In the event that the chamber sensor probe is broken or the respective connection has
been interrupted during the defrost phase the function will be completed normally.
The string set with the parameter "d6" and the label [E0] will be visualised alternatively on
the display.
Evaporator probe error
If the evaporator / defrost probe is broken or its connection is interrupted, the defrosting
phase ends due to timeout.
The evaporator fan will continue to run according to the value assigned to parameter
"F2", but however without looking at the temperature of the evaporating pack.
Drip times "d7" and internal fan activation delay "F3" are however observed.
The display shows the string set with the parameter "d6" and the label [E1] alternately.
Condenser probe error
If the condenser probe is broken or the relevant connection interrupted, the display shows
the label [E2].
The condenser fan continues to run in parallel with the compressor with delay when the
compressor is switched off if F12>0 and in any case without looking at the temperature on
the condenser.
Note: if more than one probe is broken or interrupted, the relative labels will be shown
sequentially on the display.

HIGH TEMPERATURE ALARM

If the room temperature exceeds the setpoint, the label [AH] and the
temperature reached alternate on the display. The buzzer sounds.
Press the up key while the alarm is still active to view the duration of the
alarm event.
The buzzer may be silenced by pressing the button
The visual alarm signal stays on until the temperature returns within the normal range.
LOW TEMPERATURE ALARM
If the room temperature is below the setpoint, the label [AL] and the
temperature reached alternate on the display. The buzzer sounds.
Press the down key while the alarm is still active to view the duration of
the alarm event.
The buzzer may be silenced by pressing the button