9. Level probe operation
The level probes allow tcontrol to manage the water level completely independently.
Pump protection level float A OPEN
Level-control float B OPEN
Overflow float C OPEN
Pump protection level float A OPEN
Level-control float B OPEN
Overflow float C CLOSED
Pump protection level float A OPEN
Level-control float B CLOSED
Overflow float C CLOSED
Pump protection level float A CLOSED
Level-control float B CLOSED
Overflow float C CLOSED
NOTE: A green led light on the front panel signals when the level-control valve is open
10. Frost function
The frost function is an important protection that your Tcontrol runs on its own. With any setting
(filtering on 1 or on 0 or on T or on A) if the water temperature drops below 3°C your Tcontrol starts
the frost function. AG appears on the display.
This function consists in turning the filtering system on for 3 minutes every hour, day and night. This
procedure allows you to protect the pumps and the hydraulic system and avoid ice from forming
in the pool.

TECHNICAL DATA

Power supply: 230 Vac 50Hz
Maximum overall draw: 2.9 Kw
Maximum filtering output load: 2.7 Kw
Protection rating: IP 65
Operational conditions: between -10°C and +40°C
Measurements: 300 x 240 x h140 mm
Weight: 3.5Kg
Material: ABS
Certification: EC
[OPERATION AND MAINTENANCE
MANUAL]
[V-1.16]
Overflow level: T-control forces the filtration pump to start
up
Normal operation: T-control closes the level-control
valve
Level-control: T-control opens the level-control valve
Pump protection function: T-control forces the filtration
pump to stop