¾ Start the entry by activating the function "PAr".
¾ Select the individual ciphers of the parameter number by rotat-
ing and confirm by pressing.
¾ Activate the entry by selecting "SET" and by pressing.
¾ Perform the setting according to the subsequent parameter list.
¾ Return to the basic level by selecting "BACK" 2 times.
If no operation is performed, the display returns to the basic
level after approximately 30 seconds.
No. Description
Heating system
Sets the existing heating system:
• Floor heating, standard (FBH St.)
010
• Floor heating, low energy (FBH NE)
• Radiator (RAD)
• Convector, passive (KON pas)
• Convector, active (KON akt)
Blocking of cooling
020
Deactivates the cooling function.
Operating lock
030
Protects the deactivation of the operating
lock with a PIN.
PIN operating lock
Sets the PIN for parameter 30.
If PIN is unknown:
¾ Disconnect the device from the
mains network.
031
¾ Hold down the rotary control and
apply voltage again until the soft-
ware version is shown on the dis-
play and goes out again.
¾ Press the rotary control again until
the symbol
Setting
0 = FBH St.
1 = FBH NE
2 = RAD
3 = KON pas
4 = KON akt
Standard: 0
0 = activated
1 = deactivated
Standard: 0
0 = deactivated
1 = activated
Standard: 0
0 ... 9999
Standard: 0000
disappears.