8 Technical features
COnsTrUCTiOn sPeCifiCATiOns
Weights
Dimensions L x H x P in mm
Protection
Ambient specifications
Operating temperature range
Operating relative humidity range
Degree of protection as per IEC529
Noise level at 1 meter
electrical input specifications
Rated input voltage
Range of input voltage
Rated input frequency
Maximum input current
Number of input phases
Waveform on output
With battery operation
Type of operation
electrical specifications on output
Rated output voltage
Active output capacity on nominal load
Apparent output capacity on nominal load
Overload capacity
Number of phases on output
Daker DK 1, 2, 3 kVA
3 100 50
3 100 51
16 Kg
29,5 Kg
440 x 88 x 405 440 x 88 x 650 440 x 88 x 650
Electronic protection against overloading
and short-circuiting. Shutdown on reaching
operating limit and overheating.
Automatic shutdown due to protection
triggering
from 0 to +40 °C
from 20 to 80% non-condensing
IP20
< 50 dBA
230 V
from 160 V to 288 V
50 or 60 Hz ± 5Hz
5,2 Arms
10,4 Arms
Single phase
sinusoidal
on line - double conversion
230 V ± 1%
800W
1,6 kW
1kVA
2 KWA
105% continuous
120% for 30 seconds
150% for 10 seconds
Single phase
3 100 52
30 Kg
15 Arms
2,4 kW
3 KWA
41