Installation
Output current must be less than 1.5 A! If larger, ask our technical support.
L
N
L'
Do not test the emergency function until the battery has been charged for at least 24
hours.
A test button + corresponding indicator are included in the scope of delivery for testing the
battery kit. Connect the display and test button according to the instructions. Use the bra-
cket to fix the LED display in the ceiling (hole diameter 6.5 mm / 21 mm depending on the
accessories). Then insert the bracket with the LED display into the drilled hole. Countersink
the test button into a hole in the ceiling (Ø 7 mm) and, if necessary, fix it with a nut or glue
it in place. Pressing the button briefly starts a function test for 5 sec. Charge the battery
at least 5% (30 min). Every 7 days, the emergency lighting unit, the battery and the LED
module are tested with the self-test. Initial test: The test is carried out automatically 24
hours after the initial installation. Half-year test: The test is carried out every 180 - 182
days and takes 5 days.
Function indicator LED
green
blinkt schnell grün
flashes green slowly
lights red
Flashes red quickly
flashes slowly red
flashes green and red
Phase input
Neutral conductor input
Switched L
Phase output
Neutral conductor output
driver
driver
LED
LED
Indicator
Power
EM
Test button
Neutral conductor
Phase
Output +
Output -
functional, charging process
Self test running
Endurance test runs
Luminaire fault
Battery capacity error
Battery error
Battery operation