DIP Switch
DIP Switch Settings
The PCB for the indoor unit of the Advanced series of single
zone mini-splits has a set of DIP switches that must be set
when replacing the PCB.
The replacement PCB is shipped with all switches set to the
OFF position.
Switch settings:
SW2-1 Selects remote code A or B. Normally set to the off
position for code A operation.
If two indoor units are used in the same area and the user
wishes to control them separately, switch SW2-1 of the
second unit is set to the ON position for code B operation.
The wireless remote for the second unit is also set to code B.
SW2-2 Selects room card enable or disable.
Normally set to the OFF position. Set to the ON position
when used in conjunction with a room card interface utilized
in hotel rooms.
SW-3 & SW-4 Selects eeprom code 23, 26, 33 and 35. Set to
identify the tonnage of the unit.
Settings:
9K
(23)
SW-3
12K
(26)
SW-3
15K
(33)
SW-3
18K
(33)
SW-3
24K
(35)
SW-3
PAGE 20
OFF
SW-4
OFF
OFF
SW-4
ON
ON
SW-4
OFF
ON
SW-4
OFF
ON
SW-4
ON