1. General
This interface realizes the conversion between a RS 232 or/and
RS 485 serial signal and a TCP/IP connection signal (RJ45 support
for 10/100 Base T link), including a galvanic isolation. This interface
could be used in slave MODBUS/TCP protocol (server mode),
direct connection (tunnel) in server or client mode, and is able to
send mail via SMTP protocol using simple HAYES command on
the serial line.
2. Schematic Diagram
E
TX
D
+3.3V
+5V
RX
PWR
GND
GND
GND
ISO
+5V
A
GND
ISO
RTS
+3.3V
GND
ISO
+5V
SWA2
GND
Rx
LINK
SWA3
Tx
SWA1
GND
GND
ISO
guide d'utilisation
1SNB002323R2100 Extraction
Serial Data Converter
3. Technical specifications
Power supply
24 V AC/DC
Power supply
10 V AC to 24 V AC
voltage limit
10 V DC to 34 V DC
Tolerance
-10 %, +10 %
Information
1 yellow "power on" Led
Protection
Alternative current
Consumption
< 2 Watt
(on whole range)
Galvanic isolation
RS 232-RS 485 750 V DC
Ethernet 1500 V AC
Connection
Screw-type plug-in
connector 5.08 mm
RS 232 and RS 485 Link
EIA RS 232 C/
CCITT V24/V28
Max. speed/
115200 Bauds/
Distance
15m
Galvanic isolation
750 V DC
Information
2 green Led (RxD, TxD)
Connection
SubD9 or
screw connection
Transmitter can
1 receiver
communicate with :
Ethernet Link
Interface
Ethernet 10 Base-T or 100 Base-TX
Connector
RJ45
Speed
10/100 Mbit/s, auto sensing
Distance
100 m to next switch or hub
with CAT5 cable
Galvanic isolation
1500 V AC
Information led
Activity / Speed, LINK
Physical characteristics
K
Operating temperature
0 to +60 °C
M
Storage temperature
-20 to +70 °C
L
94 3.70"
75 2.95"
6
1
51 2.01"
43 1.69"
D
E
M
e-ILPH
L
A
K
ACTIVITY
SPEED
ILPH RS 232 - RS 485 / Ethernet ISOLATED
e-ILPH
4.
Default parameters
Modbus TCP slave mode
Speed: 9600 Bauds
Redundant 24 V DC
8 Bits,1 Stop Bit, No parity
10 V DC to 34 V DC
Control of flux: No
IP Address: 10.33.152.76
Automatic programming: yes
Asynchronous list: No
Polarity inversion
SWB-1 to ON: soft configuration enable
5. Configuration
Screw connection
Two modes are available to configure this product:
(D, E, A)
- Switch mode:
(Even if you use the switch configuration you have to configure the
IP Address by software Cf. chap 5.2 Configuration by software).
- Software mode:
(All parameters configured by soft)
EIA RS 485
5.1 Configuration by Switch
115200 Bauds/
Open the box on label side to modify switch position
1200m
SWB
Speed
Speed
Speed
Speed
Screw-type
plug-in connector
Even parity
Odd parity
No parity
Parity
up to 31 receivers
1 Stop bit
2 Stop bit
simultaneously
AC31 mode enable
Disable
Modbus slave
Transparent mode
Soft config enable
Switch enable
SWB-2
ON
MODBUS/TCP slave mode
OFF
Tunnel mode (transparent mode)
SWB-3
ON
Enable to program the AC31
OFF
Disable to Program AC31
SWB-4
ON
1 Stop bit
(TCP connection)
OFF
2 Stop bits
SWB-5
ON
No parity
OFF
Parity
SWB-6
ON
Even parity
OFF
Odd parity
SWB-7 and SWB-8 (
Choose in the table beside the communication speed)
SWB-7
SWB-8
Off
Off
Configuration
Open the box on label side
On
Off
to modify switch position
Off
On
On
On
SWA-1 and SWA-2
SWB
ON
Line polarized
ON OFF
8
OFF
Line not polarized
7
SWA
6
SWA-1 and SWA-2, have to be on same position
ON OFF
5
4
4
3
3
SWA-3
ON
RS 485 End bus adaptor resistance
2
2
OFF
No RS 485 End bus adaptation
1
1
SWA-4
Not used
5.2 Configuration by Software
- Values are validated by pressing "Enter" key.
- Corrections could be done by "Backspace" key before "Enter" is
pressed.
- For each parameter, actual value is indicated into parenthesis, to
keep this value, press "Enter" key.
- Choice Y or N (Yes/No values) could be done in capital or small
letters.
Set up menu with TCP connection:
- With TELNET: Click on Start / Execute. Enter command TELNET
10.33.152.76 (or IP address already modified). The menu appears.
Type "Enter", configuration menu is started.
- With HYPERTERMINAL: Launch HyperTerminal windows, set
communication "TCP/IP (Winsock)", set IP address and port "23".
Set up with serial connection:
Connect PC to RS 232 (if SubD9 connector is used, connect with
a cross cable). Always set serial parameter to 9600 baud, 8 bits,
no parity, 1 stop bit, no flux control. Switch off e-ILPH, press "x"
key and maintain this key press while power on the e-ILPH. Then
menu mode is displayed after few seconds.
Menu description
0 – Network configuration: IP address, input address, gateway...
SWB-1 to OFF
1 – Serial Line Parameters: Speed, characters, parity...
2 – Operation Mode: Slave MODBUS/TCP, Transparent server or
client, mail mode...
SWB-1 to ON
3 – Factory defaults
4 – Exit without save
5 – Save and Exit
6 – English/French.
6. Connection
RS 232 connection
could be done wire
less on M, L, K or
SWA
SubD9 points
Not used
Speed
End resistance
No end resistance
GND line polarized
GND not polarized
VCC line polarized
VCC not polarized
With RS 232
cross TX
and RX
from the 2
devices
+24V
Power supply
Speed
9600
7. Visualization
38400
PWR
57600
LINK
115200
TXD
RXD
(GND for SWA-2, VCC for SWA-1)
SPEED
ACTIVITY
8. Special functions
- Concentrator mode (Asynchronous): In Modbus/TCP, e-ILPH is
used with an exchange table and concentrates the information.
- AC31 programming: e-ILPH could be used to program point
to point, the 40/50 series via TCP/IP connection in switching to
programming mode.
For more information please contact your seller or find the complete
documentation 1SNB 002 323 R2100 on the ABB.com
SubD9
GND
connector
RX
RX
pin 2 = RX
TX
TX
pin 3 = TX
K
pin 5 = GND
L
pin 7 = RTS
M
P W
RX
R
GN
D
TX
L IN
K
T X
D
R X
D
Et
he
rn
et
D
E
B2-
A
RS 485
B1+
0V
24V
Lights with power supply ON
RX
GND
TX
PWR
Lights during active TCP connection
LINK
Lights during emission on serial port
TXD
Lights during reception on serial port
RXD
Amber color: 10 base-T connection
Ethernet
Green color: 100 base-TX connection
Momentary amber color,
half duplex activity
Momentary green color,
full duplex activity