6.7 - CHANGE OVER MANAGEMENT

The change-over function (Summer/Winter change) allows you to switch the heating/
air conditioning season locally (display) or remotely (digital input 2).
Please note: if set from input 2, Open = Winter; Close = Summer.
12:01 01-01-18
1
23.0
1
off
ADV. PROG.
2
LIGHT ON 15S
TMP LCK:ON
LIGHT INT S
CORRECTION
DAY SAV YES
DIFF: STD
TA = 5.0
CELSIUS
RH = 57%
ITALIAN
ALR: OPEN
RESET YES
CHG O: INP
CH140 V1.0
DEW PNT: ON

6.8 - ANTI-CONDENSATE MANAGEMENT

In summer, it prevents condensate from forming on the surface of the floor by controlling
and managing the dew point.
If the supply temperature read by the floor probe reaches the dew point value corrected
by the offset parameter (O D.P.) and this condition remains for a settable amount of time
(DLY D.P.), K492DY012 switches off the air conditioning system (relay 1 = OFF). The system
will stay off for at least the settable amount of time (TMR D.P.).
You can set the O D.P. parameter based on the type of radiant system being managed
(i.e.: wall, ceiling, or floor).
Please note: a floor probe K463PY001 must be installed.
When the Dew Point function is active during air conditioning,
the display flashes the symbol H.
WEEKLY PROGRAMMABLE THERMOSTAT
CHG O: ---
2s
■ --- = from display
■ INP = from input 2
CHG O: INP
PRESS
x6
12:01 01-01-18
PRESS
23.0
27