Indicators
LED "Power":
on when supply connected
LED K1/K2:
on when relay K1 and K2 energized
Technical Data
Input
Nominal voltage U
:
N
Nominal frequency:
Voltage range:
at 10 % residual ripple:
at 48 % residual ripple:
Nominal consumption
DC:
AC:
Control voltage on Y1
DC:
AC:
Control current
DC:
AC:
Recovery time:
Output
Contacts
LG 5924.02:
LG 5924.04:
LG 5924.48:
Operate delay
DC:
AC V:
Release delay
DCV:
AC:
Nominal output voltage:
Thermal current I
:
th
see datasheet LG 5924 on www.dold.com
*
)
Switching capacity
to AC 15
NO contact:
NC contact:
to DC 13
NO contact:
NC contact:
Electrical life
at 5 A, AC 230 V cos ϕ = 1:
Permissible operating
frequency:
Short circuit strength
max. fuse rating:
line circuit breaker:
General Data
Operating mode:
Temperature range
operation:
storage :
altitude:
Clearance and creepage
distances
rated impuls voltage /
pollution degree:
EMC
Electrostatic discharge:
HF irradiation:
Fast transients:
Surge voltages
between wires for
power supply:
between wire and ground:
HF wire guided:
Interference suppression
DC 24 V *
)
AC 110, 230 V *
)
*
see device label
)
50 / 60 Hz
AC 0.85 ... 1.1 U
N
DC 0.9 ... 1.1 U
N
DC 0.85 ... 1.1 U
N
DC 1.5 W
3.5 VA
typ. DC 22 V
typ. DC 45 V
typ. DC 65 mA
typ. AC 16 mA
0.5 s
2 NO contacts
4 NO contacts
3 NO, 1 NC contacts
The NO contacts are safety contacts.
ATTENTION! The NC contacts 41-42
can only be used for monitoring.
typ. DC 40 ms
typ. AC 200 ms
typ. DC 70 ms
typ. AC 35 ms
max. AC 250 V
max. 5 A
(see quadratic total current limit curve)*
3 A / AC 230 V
IEC/EN 60 947-5-1
2 A / AC 230 V
IEC/EN 60 947-5-1
2 A / DC 24 V
IEC/EN 60 947-5-1
2 A / DC 24 V
IEC/EN 60 947-5-1
> 2.2 x 10
switching cycles
5
600 switching cycles / h
10 A gL
IEC/EN 60 947-5-1
B 6 A
Continuous operation
- 15 ... + 55 °C
- 25 ... + 85 °C
< 2.000 m
4 kV / 2 (basis insulation) IEC 60 664-1
8 kV (air)
IEC/EN 61 000-4-2
10 V / m
IEC/EN 61 000-4-3
2 kV
IEC/EN 61 000-4-4
1 kV
IEC/EN 61 000-4-5
2 kV
IEC/EN 61 000-4-5
10 V
IEC/EN 61 000-4-6
Limit value class B
EN 55011
Technical Data
Degree of protection
Housing:
Terminals:
Housing:
Vibration resistance:
Climate resistance:
Terminal designation:
Wire fixing:
Mounting:
Weight
LG 5924, DC 24 V:
LG 5924, AC 230 V:
UL-Data
The safety functions were not evaluated by UL. Listing is accom-
plished according to requirements of Standard UL 508, "general use
applications"
Nominal voltage U
:
N
Ambient temperature:
Switching capacity:
Ambient temperature 45°C:
Ambient temperature 55°C:
Wire connection:
Screw terminals fixed:
Plug in screw:
Plug in cage clamp:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
)
nfo
Troubleshooting
Failure
LED "Power" does not light up
LED "K1/K2" does not light up
Device cannot be activated
Maintenance and repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
4
IP 40
IEC/EN 60 529
IP 20
IEC/EN 60 529
Thermoplastic with V0 behaviour
according to UL subject 94
Amplitude 0.35 mm
frequency 10 ... 55 Hz, IEC/EN 60 068-2-6
15 / 055 / 04
IEC/EN 60 068-1
EN 50 005
Plus-minus terminal screws M 3.5
box terminals with wire protection or
cage clamp terminals
DIN rail
IEC/EN 60 715
200 g
270 g
DC 24 V
AC 110, 230 V
-15 ... +55°C
Pilot duty B300
5A 250Vac Resistive
5A 24Vdc Resistive or G.P.
Pilot duty B300
4A 250Vac Resistive
4A 24Vdc Resistive or G.P.
60°C / 75°C copper conductors only
AWG 20 - 12 Sol/Str Torque 0.8 Nm
AWG 20 - 14 Sol Torque 0.8 Nm
AWG 20 - 16 Str Torque 0.8 Nm
AWG 20 - 12 Sol/Str
Potential cause
Power supply not connected
Relay K1 and K2 not energized
- Supply voltage is not present
- Defective On-button e.g. no bridge
at Y1 and Y2
- K1 or K2 are welded
LG 5924 / 130103 / 299