Tripp-Lite SmartOnline SU12000RT4U Manuel Du Propriétaire page 14

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operation
(continued)
Overload Messages
When the UPS detects an output overload, its LCD will switch to the following display:
The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to BYPASS
MODE to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:
Bypass Messages
While in BYPASS MODE, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS will not
provide battery backup in BYPASS MODE. If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than
nominal), the UPS displays the condition on its LCD and stops supplying output power to its load.
201102169 93-2676.indd 14
OVERLOAD!
LOAD1 = XXX% X.XKW
OVERLOAD!
LOAD2 = XXX% X.XKW
Overload Condition
102% - 125%
125% - 150%
> 150%
Bypass Voltage Conditions
L1 > 15% Higher
Than Nominal Voltage
L2 > 15% Higher
Than Nominal Voltage
L1 > 20% Lower
Than Nominal Voltage
L2 > 20% Lower
Than Nominal Voltage
L1 Voltage Was Too High,
Now Returned to Nominal Voltage
L2 Voltage Was Too High,
Now Returned to Nominal Voltage
L1 Voltage Was Too Low,
Now Returned to Nominal Voltage
L2 Voltage Was Too Low,
Now Returned to Nominal Voltage
Countdown Duration
1 minute
30 seconds
Immediate Bypass
LCD Screen Messages
BYPASS AC1 HIGH
LOAD1 = XXX% X.XKW
BYPASS AC2 HIGH
LOAD1 = XXX% X.XKW
BYPASS AC1 LOW
LOAD1 = XXX% X.XKW
BYPASS AC2 LOW
LOAD1 = XXX% X.XKW
BYPASS AC1 WAS HI
LOAD1 = XXX% X.XKW
BYPASS AC2 WAS HI
LOAD1 = XXX% X.XKW
BYPASS AC1 WAS LO
LOAD1 = XXX% X.XKW
BYPASS AC2 WAS LO
LOAD1 = XXX% X.XKW
14
3/29/2011 5:08:33 PM

Publicité

Table des Matières
loading

Table des Matières