Energy meter on CT/1A - /5A,
indirect connection
1. USE
Bidirectional active and reactive energy meter (4 quadrants).
Indirect connection through /1A - /5A ratio current transformers.
The device, 4 DIN modules, is self-powered and has ModBus or
Mbus communication or pulse output and double tariff input.
On the menu it is possible to select the device configuration for
operation with the different types of connections (3N3E;3-3E;3-2E).
2. RANGE
Code Art.
In
Output
CE4TB0PCL1
Pulse
1/5A
CE4TBDTCL1
ModBus
1/5A
CE4TBMTCL1
MBus
1/5A
3. INSTALLATION
Fixing:
On EN/IEC 60715 symmetric rail or DIN 35 rail.
Necessary tools:
For fastening the device on the DIN rail: 5.5 mm flat screwdriver
(from 4 to 6 mm).
Operating position:
Vertical,
Horizontal,
Upside down,
Technical data sheet: IDP000191EN_05
Input
Range Voltage
Pulse
3x100V 3x230V 3x400V ± 15%
2 Tariff
3x100V 3x230V 3x400V ± 15%
2 Tariff
3x100V 3x230V 3x400V ± 15%
On the side
Updated: 20/04/2021
BTicino
SpA
Viale Borri 231, 21100 Varese - Italia
www.imeitaly.com
Codes: CE4TBDTCL1 - CE4TB0PCL1 - CE4TBMTCL1
Model: CONTO D4-Pt
Contents
1. Use ..................................................................... 1
2. Range ................................................................. 1
3. Installation .......................................................... 1
4. Dimensions......................................................... 1
5. Connections ....................................................... 2
4. DIMENSIONS
Housing:
4 DIN43880 modules
66,0 mm
49,2 mm
Pages
71,2 mm
Created: 19/03/2019
1 | 8